BACnet object reference
BACnet object types: numbers, properties and the priority array
Everything a BACnet device shows is an object of a standard type: analog inputs for sensors, binary outputs for start/stop, schedules, trend logs, the device object itself. These pages give each common type's number, its properties with their identifiers, how commanding and COV work for it, what goes wrong on site, and how to read, write and watch it in OTDeck's BACnet client.
Object types
| Type | Object | Abbr. | Present_Value | Commandable |
|---|---|---|---|---|
| 0 | Analog Input | AI | REAL | No |
| 1 | Analog Output | AO | REAL | Always |
| 2 | Analog Value | AV | REAL | Optional |
| 3 | Binary Input | BI | BACnetBinaryPV | No |
| 4 | Binary Output | BO | BACnetBinaryPV | Always |
| 5 | Binary Value | BV | BACnetBinaryPV | Optional |
| 6 | Calendar | CAL | BOOLEAN | No |
| 8 | Device | DEV | None | No |
| 9 | Event Enrollment | EE | None | No |
| 12 | Loop | LP | REAL | No |
| 13 | Multi-state Input | MSI | Unsigned | No |
| 14 | Multi-state Output | MSO | Unsigned | Always |
| 15 | Notification Class | NC | None | No |
| 17 | Schedule | SCH | Any primitive datatype | No |
| 19 | Multi-state Value | MSV | Unsigned | Optional |
| 20 | Trend Log | TL | None | No |
| 23 | Accumulator | ACC | Unsigned | No |
| 56 | Network Port | NP | None | No |
Properties every object has
Object_Identifier (75) is the type and instance, analog-input,1. Object_Name (77) is unique within the device; Object_Type (79) repeats the type; Description (28) is optional free text. Devices of protocol revision 14 and later list an object's properties in Property_List (371), which is the reliable way to know which optional properties a device implements.
Point objects (inputs, outputs and values) also carry Status_Flags (111: in-alarm, fault, overridden, out-of-service), Event_State (36), Out_Of_Service (81) and often Reliability (103). Analog points add Units (117) and COV_Increment (22); binary points Active_Text (4) and Inactive_Text (46); multi-state points Number_Of_States (74) and State_Text (110).
The priority array
A commandable object has a Priority_Array (87) of 16 slots and a Relinquish_Default (104). Each WriteProperty to Present_Value carries a priority (16 when it carries none) and fills that slot; the highest-priority slot that is not NULL becomes Present_Value. Writing NULL at a priority relinquishes the slot; with all 16 empty, Present_Value is Relinquish_Default.
| Priority | Use in ASHRAE 135 |
|---|---|
| 1 | Manual-Life Safety |
| 2 | Automatic-Life Safety |
| 3 | Available |
| 4 | Available |
| 5 | Critical Equipment Control |
| 6 | Minimum On/Off |
| 7 | Available |
| 8 | Manual Operator |
| 9–16 | Available (16 is used when a write carries no priority) |
OTDeck writes at priority 16 by default and refuses priorities 1 to 8 unless the connection allows them, for the app and for AI agents alike.
COV
A client subscribes with SubscribeCOV and the device notifies it of changes of Present_Value and Status_Flags: for analog objects when the value moved by at least COV_Increment, for binary and multi-state objects on every change. OTDeck's watch list subscribes this way and polls the objects a device refuses to report.
FAQ
What are the BACnet object types?
ASHRAE 135 defines the standard object types by number: analog input 0, analog output 1, analog value 2, binary input 3, binary output 4, binary value 5, calendar 6, device 8, event enrollment 9, loop 12, multi-state input 13, multi-state output 14, notification class 15, schedule 17, multi-state value 19, trend log 20, accumulator 23, network port 56, and more. Numbers from 128 up are vendor-proprietary.
Which BACnet objects are commandable?
Analog, binary and multi-state outputs always are. Analog, binary and multi-state values are commandable when they have Priority_Array and Relinquish_Default. Inputs never are.
What is the BACnet priority array?
Sixteen slots on the Present_Value of a commandable object. Each command writes into one slot; the highest-priority slot that is not NULL becomes Present_Value, and when all are NULL the object takes Relinquish_Default. Priority 1 is the highest; a write without a priority goes to 16.