BACnet object reference · type 9
BACnet Event Enrollment object (type 9): algorithmic alarms
The BACnet event enrollment object puts an alarm on a property of another object: an out-of-range check, a change-of-state watch, a command-failure test. It is the way to alarm on objects that have no intrinsic reporting of their own.
- Object type
- 9 (event-enrollment)
- Common abbreviation
- EE
- Present_Value
- None
- Commandable
- No
- COV
- No
- In OTDeck
- event-enrollment:1
What it is
Intrinsic reporting builds the alarm into the object (High_Limit on an analog input). Algorithmic reporting puts it into an event enrollment: the enrollment monitors Object_Property_Reference with the algorithm in Event_Type and the settings in Event_Parameters.
Object type 9 in ASHRAE 135.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Event Enrollment object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Event_Type | 37 | yes | The algorithm: change-of-bitstring, change-of-state, change-of-value, command-failure, floating-limit, out-of-range, buffer-ready, unsigned-range and others. |
| Event_Parameters | 83 | yes | The algorithm's settings, for example time delay, low limit, high limit and deadband for out-of-range. |
| Object_Property_Reference | 78 | yes | The monitored object and property, possibly in another device. |
| Event_State | 36 | yes | normal, offnormal, high-limit, low-limit or fault. |
| Event_Enable | 35 | yes | Which transitions are reported. |
| Acked_Transitions | 0 | yes | Which transitions have been acknowledged. |
| Notify_Type | 72 | yes | alarm or event. |
| Event_Time_Stamps | 130 | yes | When each of the three transitions last happened. |
| Notification_Class | 17 | The notification-class object whose priorities, acknowledgement rules and recipients this object's alarms use. |
Worked example: An out-of-range alarm on a space temperature
An event enrollment that watches the Present_Value of a room's analog value with the out-of-range algorithm. Event_Parameters hold the settings below.
| Setting or moment | Value and effect |
|---|---|
| Object_Property_Reference | analog-value:12, Present_Value (the room temperature). |
| Event_Parameters | out-of-range: Time_Delay 300 s, Low_Limit 18.0, High_Limit 26.0, Deadband 0.5. |
| Notification_Class | 3, whose Recipient_List names the head-end and, during commissioning, OTDeck. |
| 14:02 the value reaches 26.4 | Nothing yet: the condition must last Time_Delay (5 minutes). |
| 14:07 still above 26.0 | Event_State becomes high-limit; a to-offnormal notification goes to every recipient of class 3. |
| 14:20 the value falls to 25.8 | Still high-limit: the return needs the value below High_Limit minus Deadband, 25.5. |
| 14:31 the value is 25.3 for 5 minutes | Event_State returns to normal and a to-normal notification is sent, if Event_Enable includes it. |
If the controller that holds analog-value:12 goes offline, the enrollment cannot read it and goes to fault, a different transition with its own acknowledgement.
Commanding
An event enrollment is configured, not commanded; it has no Present_Value and no priority array.
COV
Event enrollments do not report COV. Their state changes go out as event notifications through the notification class.
Typical uses in HVAC and BMS
- Alarms on values that have no limits of their own, such as a calculated value.
- Floating-limit alarms that follow a setpoint (space temperature off setpoint by more than 2 K).
- Alarms on a point in another controller.
Field pitfalls
- Object_Property_Reference to another device: when that device is offline the enrollment goes to fault, not to normal.
- Notification_Class pointing at a class that does not exist, or one whose Recipient_List is empty: the alarm triggers but nobody is told.
- Two alarms for the same condition, one intrinsic and one by enrollment, each needing acknowledgement.
Reading, writing and watching it in OTDeck
- Select event-enrollment:N to read Event_Type, Event_Parameters, the monitored reference, Event_State and the rest.
- The Alarms tab reads GetEventInformation, which lists enrollments that are not normal or wait for acknowledgement, with their transitions and time stamps; Ack sends AcknowledgeAlarm (Pro, in the write log as bacnet.ack).
- The Alarms tab's Configured view lists the enrollment among the objects that report events, with its notification class, time delay and the transitions it reports, and marks one whose notification class is missing or that never reports the return to normal.
- From an alarm in the Active view you can open the object or trend it; Recipients shows who the enrollment's notification class tells.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
What is the difference between intrinsic and algorithmic reporting in BACnet?
Intrinsic reporting is built into the monitored object (limits on an analog input). Algorithmic reporting uses a separate event enrollment object that watches a property of another object.
Which alarm types can a BACnet event enrollment use?
The event algorithms of the standard, such as out-of-range, floating-limit, change-of-state, change-of-value, command-failure, buffer-ready and unsigned-range, set by Event_Type.
Why does a BACnet event enrollment go to fault?
Because it cannot evaluate the monitored property: the referenced object or device does not answer, the property does not exist, or the monitored object reports a fault of its own through Reliability.
Related object types
Download OTDeck, free for one connection BACnet client All object types
Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.