BACnet Event Enrollment object (type 9): algorithmic alarms

The BACnet event enrollment object puts an alarm on a property of another object: an out-of-range check, a change-of-state watch, a command-failure test. It is the way to alarm on objects that have no intrinsic reporting of their own.

Object type
9 (event-enrollment)
Common abbreviation
EE
Present_Value
None
Commandable
No
COV
No
In OTDeck
event-enrollment:1

What it is

Intrinsic reporting builds the alarm into the object (High_Limit on an analog input). Algorithmic reporting puts it into an event enrollment: the enrollment monitors Object_Property_Reference with the algorithm in Event_Type and the settings in Event_Parameters.

Object type 9 in ASHRAE 135.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Event Enrollment object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Event_Type37yesThe algorithm: change-of-bitstring, change-of-state, change-of-value, command-failure, floating-limit, out-of-range, buffer-ready, unsigned-range and others.
Event_Parameters83yesThe algorithm's settings, for example time delay, low limit, high limit and deadband for out-of-range.
Object_Property_Reference78yesThe monitored object and property, possibly in another device.
Event_State36yesnormal, offnormal, high-limit, low-limit or fault.
Event_Enable35yesWhich transitions are reported.
Acked_Transitions0yesWhich transitions have been acknowledged.
Notify_Type72yesalarm or event.
Event_Time_Stamps130yesWhen each of the three transitions last happened.
Notification_Class17The notification-class object whose priorities, acknowledgement rules and recipients this object's alarms use.

Worked example: An out-of-range alarm on a space temperature

An event enrollment that watches the Present_Value of a room's analog value with the out-of-range algorithm. Event_Parameters hold the settings below.

Setting or momentValue and effect
Object_Property_Referenceanalog-value:12, Present_Value (the room temperature).
Event_Parametersout-of-range: Time_Delay 300 s, Low_Limit 18.0, High_Limit 26.0, Deadband 0.5.
Notification_Class3, whose Recipient_List names the head-end and, during commissioning, OTDeck.
14:02 the value reaches 26.4Nothing yet: the condition must last Time_Delay (5 minutes).
14:07 still above 26.0Event_State becomes high-limit; a to-offnormal notification goes to every recipient of class 3.
14:20 the value falls to 25.8Still high-limit: the return needs the value below High_Limit minus Deadband, 25.5.
14:31 the value is 25.3 for 5 minutesEvent_State returns to normal and a to-normal notification is sent, if Event_Enable includes it.

If the controller that holds analog-value:12 goes offline, the enrollment cannot read it and goes to fault, a different transition with its own acknowledgement.

Commanding

An event enrollment is configured, not commanded; it has no Present_Value and no priority array.

COV

Event enrollments do not report COV. Their state changes go out as event notifications through the notification class.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

What is the difference between intrinsic and algorithmic reporting in BACnet?

Intrinsic reporting is built into the monitored object (limits on an analog input). Algorithmic reporting uses a separate event enrollment object that watches a property of another object.

Which alarm types can a BACnet event enrollment use?

The event algorithms of the standard, such as out-of-range, floating-limit, change-of-state, change-of-value, command-failure, buffer-ready and unsigned-range, set by Event_Type.

Why does a BACnet event enrollment go to fault?

Because it cannot evaluate the monitored property: the referenced object or device does not answer, the property does not exist, or the monitored object reports a fault of its own through Reliability.