BACnet Trend Log object (type 20): Log_Buffer and ReadRange

The BACnet trend log object records one property of one object over time, inside the controller, so history survives without a BMS connected. The records sit in Log_Buffer and are read with the ReadRange service.

Object type
20 (trend-log)
Common abbreviation
TL
Present_Value
None; the data is in Log_Buffer
Commandable
No
COV
Not for the log itself; it can log its source by COV (Logging_Type cov)
In OTDeck
trend-log:1 or tl:1

What it is

A trend log samples a property (Log_DeviceObjectProperty, usually a Present_Value) every Log_Interval, on each change of value, or when triggered, and stores time-stamped records in a ring buffer of Buffer_Size records.

Object type 20 in ASHRAE 135. Trend Log Multiple (type 27) logs several properties per record.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Trend Log object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Enable133yesFALSE stops logging. Formerly named Log_Enable.
Log_DeviceObjectProperty132The object and property logged, possibly in another device.
Logging_Type197polled (every Log_Interval), cov (on each change) or triggered.
Log_Interval134The sampling period in hundredths of a second: 6000 is one minute.
Buffer_Size126yesHow many records the buffer holds.
Log_Buffer131yesThe records: time stamp, value (or a log status, failure or time change) and optional status flags. Read with ReadRange.
Record_Count141yesRecords in the buffer now. Writing 0 clears the buffer.
Total_Record_Count145yesRecords ever logged; the sequence number of the newest record.
Stop_When_Full144yesTRUE stops logging when the buffer is full; FALSE overwrites the oldest records.
Start_Time142Logging starts at this time, when set.
Stop_Time143Logging stops at this time, when set.
Notification_Threshold137Records after which a buffer-ready notification goes out.
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Event_State36yesnormal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault).

Commanding

A trend log has no Present_Value and no priority array. Enable, Record_Count and the timing properties are written directly by configuration tools.

COV

With Logging_Type cov, the trend log subscribes to its source and logs each notification; the source's COV_Increment then decides the resolution of the log.

A client gets new records by reading again from where it stopped, or by subscribing to buffer-ready notifications through a notification class.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

How do you read a BACnet trend log?

With the ReadRange service on Log_Buffer: by position (N records from an index), by time (records from a time stamp) or by sequence number. ReadProperty on Log_Buffer is refused by many devices.

What unit is BACnet Log_Interval in?

Hundredths of a second. A one-minute log has Log_Interval 6000.

What happens when a BACnet trend log is full?

With Stop_When_Full FALSE the oldest records are overwritten; with TRUE logging stops until the buffer is cleared, for example by writing 0 to Record_Count.

Related object types

Download OTDeck, free for one connection BACnet client All object types