BACnet object reference · type 20
BACnet Trend Log object (type 20): Log_Buffer and ReadRange
The BACnet trend log object records one property of one object over time, inside the controller, so history survives without a BMS connected. The records sit in Log_Buffer and are read with the ReadRange service.
- Object type
- 20 (trend-log)
- Common abbreviation
- TL
- Present_Value
- None; the data is in Log_Buffer
- Commandable
- No
- COV
- Not for the log itself; it can log its source by COV (Logging_Type cov)
- In OTDeck
- trend-log:1 or tl:1
What it is
A trend log samples a property (Log_DeviceObjectProperty, usually a Present_Value) every Log_Interval, on each change of value, or when triggered, and stores time-stamped records in a ring buffer of Buffer_Size records.
Object type 20 in ASHRAE 135. Trend Log Multiple (type 27) logs several properties per record.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Trend Log object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Enable | 133 | yes | FALSE stops logging. Formerly named Log_Enable. |
| Log_DeviceObjectProperty | 132 | The object and property logged, possibly in another device. | |
| Logging_Type | 197 | polled (every Log_Interval), cov (on each change) or triggered. | |
| Log_Interval | 134 | The sampling period in hundredths of a second: 6000 is one minute. | |
| Buffer_Size | 126 | yes | How many records the buffer holds. |
| Log_Buffer | 131 | yes | The records: time stamp, value (or a log status, failure or time change) and optional status flags. Read with ReadRange. |
| Record_Count | 141 | yes | Records in the buffer now. Writing 0 clears the buffer. |
| Total_Record_Count | 145 | yes | Records ever logged; the sequence number of the newest record. |
| Stop_When_Full | 144 | yes | TRUE stops logging when the buffer is full; FALSE overwrites the oldest records. |
| Start_Time | 142 | Logging starts at this time, when set. | |
| Stop_Time | 143 | Logging stops at this time, when set. | |
| Notification_Threshold | 137 | Records after which a buffer-ready notification goes out. | |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Event_State | 36 | yes | normal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault). |
Commanding
A trend log has no Present_Value and no priority array. Enable, Record_Count and the timing properties are written directly by configuration tools.
COV
With Logging_Type cov, the trend log subscribes to its source and logs each notification; the source's COV_Increment then decides the resolution of the log.
A client gets new records by reading again from where it stopped, or by subscribing to buffer-ready notifications through a notification class.
Typical uses in HVAC and BMS
- Supply temperature, space temperature and valve positions for tuning and troubleshooting.
- Energy meters logged every 15 minutes.
- Proof of operation during commissioning and seasonal tests.
Field pitfalls
- Log_Buffer read with ReadProperty: the standard has it read with ReadRange; many devices refuse it, others return a huge segmented answer.
- Log_Interval read as seconds: it is in hundredths, so 100 means one second.
- Enable FALSE or Stop_When_Full TRUE with a full buffer: the log looks fine but has not recorded since.
- A device clock that was wrong when the records were made: a by-time read misses them. Read by position instead.
Reading, writing and watching it in OTDeck
- The Trend log tab reads Log_Buffer with ReadRange: the last N records (Record_Count read first), N records from a position, or a time range; up to 10 000 records per read, 100 per page.
- Records show their time, value, kind (real, boolean, log-status, failure…) and status flags, in a table and on a chart. Reading is free; Export CSV is Pro.
- Devices that refuse ReadRange by time are read by position and filtered; pages are halved for devices with small APDUs; time stamps use the device's UTC_Offset and daylight saving status.
- AI agents read trend logs through read_history.
- The simulator's trend-log:1 logs the supply temperature every second into a 3600-record buffer.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
How do you read a BACnet trend log?
With the ReadRange service on Log_Buffer: by position (N records from an index), by time (records from a time stamp) or by sequence number. ReadProperty on Log_Buffer is refused by many devices.
What unit is BACnet Log_Interval in?
Hundredths of a second. A one-minute log has Log_Interval 6000.
What happens when a BACnet trend log is full?
With Stop_When_Full FALSE the oldest records are overwritten; with TRUE logging stops until the buffer is cleared, for example by writing 0 to Record_Count.