BACnet Accumulator object (type 23): meter pulses

The BACnet accumulator object counts pulses, typically from an energy, water or gas meter. Present_Value is an unsigned count; Scale turns it into engineering units such as kWh or m³.

Object type
23 (accumulator)
Common abbreviation
ACC
Present_Value
Unsigned: the count; Present_Value × Scale is the value in Units
Commandable
No
COV
Device-dependent; poll if the device refuses SubscribeCOV
In OTDeck
accumulator:1

What it is

An accumulator counts input pulses, optionally divided first by Prescale, and rolls over after Max_Pres_Value. It keeps the count as an integer so no precision is lost on long totals.

Object type 23 in ASHRAE 135. The related Pulse Converter (type 24) presents the same kind of input as a REAL already in engineering units.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Accumulator object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Present_Value85yesThe count.
Scale187yesThe factor that converts the count to Units: a REAL factor, or an integer power of ten.
Units117yesAn enumeration, not text: 62 is degrees-Celsius, 64 degrees-Fahrenheit, 98 percent, 29 percent-relative-humidity, 54 kilopascals, 95 no-units.
Prescale185How many input pulses make one count (a multiplier and a modulo divide).
Max_Pres_Value65yesThe highest count before the value rolls over.
Value_Change_Time192When Present_Value was last set by a write to Value_Set.
Value_Before_Change190The count just before that write.
Value_Set191Writing it sets the count, for example to match a meter's display.
Logging_Record184A snapshot of the count with a time stamp, for meter reading.
Pulse_Rate186Pulses counted in the last Limit_Monitoring_Interval, for rate alarms.
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Event_State36yesnormal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault).
Out_Of_Service81yesTRUE decouples the count from the pulse input.

Commanding

An accumulator has no priority array. The count is adjusted through Value_Set (where the device provides it), not by commanding Present_Value.

COV

Some devices report accumulators by COV, others only answer reads. A meter that pulses once a minute is cheap to poll.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

How do you convert a BACnet accumulator count to kWh?

Multiply Present_Value by the Scale property; Units gives the unit of the result. Scale is either a REAL factor or an integer power of ten.

What is the difference between an accumulator and a pulse converter?

An accumulator keeps an unsigned count with a separate Scale. A pulse converter (type 24) presents a REAL already scaled to engineering units.

Related object types

Download OTDeck, free for one connection BACnet client All object types

Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.