BACnet object reference · type 23
BACnet Accumulator object (type 23): meter pulses
The BACnet accumulator object counts pulses, typically from an energy, water or gas meter. Present_Value is an unsigned count; Scale turns it into engineering units such as kWh or m³.
- Object type
- 23 (accumulator)
- Common abbreviation
- ACC
- Present_Value
- Unsigned: the count; Present_Value × Scale is the value in Units
- Commandable
- No
- COV
- Device-dependent; poll if the device refuses SubscribeCOV
- In OTDeck
- accumulator:1
What it is
An accumulator counts input pulses, optionally divided first by Prescale, and rolls over after Max_Pres_Value. It keeps the count as an integer so no precision is lost on long totals.
Object type 23 in ASHRAE 135. The related Pulse Converter (type 24) presents the same kind of input as a REAL already in engineering units.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Accumulator object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Present_Value | 85 | yes | The count. |
| Scale | 187 | yes | The factor that converts the count to Units: a REAL factor, or an integer power of ten. |
| Units | 117 | yes | An enumeration, not text: 62 is degrees-Celsius, 64 degrees-Fahrenheit, 98 percent, 29 percent-relative-humidity, 54 kilopascals, 95 no-units. |
| Prescale | 185 | How many input pulses make one count (a multiplier and a modulo divide). | |
| Max_Pres_Value | 65 | yes | The highest count before the value rolls over. |
| Value_Change_Time | 192 | When Present_Value was last set by a write to Value_Set. | |
| Value_Before_Change | 190 | The count just before that write. | |
| Value_Set | 191 | Writing it sets the count, for example to match a meter's display. | |
| Logging_Record | 184 | A snapshot of the count with a time stamp, for meter reading. | |
| Pulse_Rate | 186 | Pulses counted in the last Limit_Monitoring_Interval, for rate alarms. | |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Event_State | 36 | yes | normal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault). |
| Out_Of_Service | 81 | yes | TRUE decouples the count from the pulse input. |
Commanding
An accumulator has no priority array. The count is adjusted through Value_Set (where the device provides it), not by commanding Present_Value.
COV
Some devices report accumulators by COV, others only answer reads. A meter that pulses once a minute is cheap to poll.
Typical uses in HVAC and BMS
- Electricity meters with a pulse output (Wh per pulse).
- Water and gas meters with reed contacts.
- Run counts and production counts.
Field pitfalls
- Reading the count as kWh: multiply by Scale first. A Scale of 0.1 or a power of ten -1 makes a factor 10 difference.
- Rollover at Max_Pres_Value: a consumption calculation over the rollover goes negative unless it handles the wrap.
- Prescale set in the device and the meter's pulse value set again in the BMS: the totals are off by the factor twice.
Reading, writing and watching it in OTDeck
- Select accumulator:1 in the object tree: OTDeck reads every property the device lists (Property_List, or the standard set on older devices) with ReadPropertyMultiple, and shows Present_Value large with its units and status flags.
- Watch it: the watch list subscribes with SubscribeCOV (lifetime 300 s, renewed while watched) and falls back to polling when the device refuses; the value goes to the trend panel next to MQTT, Modbus and OPC UA values.
- Scale, Prescale, Max_Pres_Value and the other properties are in the property table. Writes in OTDeck 0.7 go to Present_Value only; Value_Set is not written.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
How do you convert a BACnet accumulator count to kWh?
Multiply Present_Value by the Scale property; Units gives the unit of the result. Scale is either a REAL factor or an integer power of ten.
What is the difference between an accumulator and a pulse converter?
An accumulator keeps an unsigned count with a separate Scale. A pulse converter (type 24) presents a REAL already scaled to engineering units.
Related object types
Download OTDeck, free for one connection BACnet client All object types
Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.