BACnet object reference · type 8
BACnet Device object (type 8): instance, Object_List and capabilities
Every BACnet device has exactly one device object. Its instance is the device's address on the BACnet internetwork, and its properties describe who made it, what it supports and which objects it holds.
- Object type
- 8 (device)
- Common abbreviation
- DEV
- Present_Value
- None
- Commandable
- No
- COV
- No
- In OTDeck
- device:1 or dev:1
What it is
The device object identifies the controller (device instance 0 to 4194302; 4194303 is the wildcard) and lists its other objects in Object_List. A BMS reads it first, on discovery, and again when Database_Revision changes.
Object type 8 in ASHRAE 135. The device instance must be unique on the whole internetwork, not only on one subnet.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Device object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Object_Identifier | 75 | yes | device,N: N is the device instance used in Who-Is ranges. |
| Object_Name | 77 | yes | Unique on the internetwork, like the instance. |
| System_Status | 112 | yes | operational, operational-read-only, download-required, download-in-progress, non-operational, backup-in-progress. |
| Vendor_Name | 121 | yes | The manufacturer as text. |
| Vendor_Identifier | 120 | yes | The manufacturer's number assigned by ASHRAE. |
| Model_Name | 70 | yes | The product. |
| Firmware_Revision | 44 | yes | Firmware version. |
| Application_Software_Version | 12 | yes | Version of the application loaded into the controller. |
| Protocol_Revision | 139 | yes | Which revision of BACnet the device implements; Property_List exists from revision 14. |
| Protocol_Services_Supported | 97 | yes | A bit string of the services the device executes: ReadPropertyMultiple, SubscribeCOV, ReadRange… |
| Protocol_Object_Types_Supported | 96 | yes | A bit string of the object types it can have. |
| Object_List | 76 | yes | Every object in the device; index 0 holds the count, so a long list can be read element by element. |
| Max_APDU_Length_Accepted | 62 | yes | The largest message it takes: 50, 128, 206, 480, 1024 or 1476 bytes. |
| Segmentation_Supported | 107 | yes | segmented-both, segmented-transmit, segmented-receive or no-segmentation. |
| APDU_Timeout | 11 | yes | Milliseconds the device waits for an answer before retrying. |
| Number_Of_APDU_Retries | 73 | yes | How often it retries. |
| Database_Revision | 155 | yes | Goes up when objects are created, deleted or renamed, or the configuration changes: the signal to re-read the device. |
| UTC_Offset | 119 | Minutes between local time and UTC; vendors disagree on the sign. | |
| Daylight_Savings_Status | 24 | TRUE while daylight saving time is in effect. |
Worked example: What to check in a device object on site
Reading the device object first saves time on every other request. These properties answer the usual questions.
| Property | What it tells you |
|---|---|
| Vendor_Name, Model_Name, Firmware_Revision | Whether the controller is the one on the submittal, and whether the firmware has the fix you were promised. |
| Protocol_Revision | Which edition of the standard the device follows: later revisions add objects and properties (network port, BACnet/SC) and date wildcards, so an old revision explains a missing property. |
| Max_APDU_Length_Accepted | 1476 on BACnet/IP, often 480 or less for an MS/TP device behind a router. Long ReadPropertyMultiple requests must fit. |
| Segmentation_Supported | no-segmentation means a large Object_List cannot be read in one go: read Object_List[0] for the count, then index by index. |
| APDU_Timeout, Number_Of_APDU_Retries | How long the device waits for confirmations, so your client's timeout matches it on slow MS/TP trunks. |
| Database_Revision | Changes when objects are added, deleted or renamed: compare it with your last export to know whether the point list changed. |
| Local_Time, UTC_Offset | Whether schedules and calendars will switch at the right hour. |
Commanding
The device object is not commanded. Device-level actions (time synchronisation, reinitialize, communication control) are separate services, not property writes.
COV
The device object reports no COV. Re-read it after a restart or when Database_Revision changes.
Typical uses in HVAC and BMS
- Discovery: Who-Is and I-Am carry the device instance; the device object then says what the device is.
- Inventory and documentation of a site's controllers.
- Checking capabilities before a BMS integration: RPM, COV, ReadRange, segmentation.
Field pitfalls
- Duplicate device instances on two controllers: the BMS talks to whichever answered last. Instances must be unique site-wide.
- Max_APDU 206 or 480 without segmentation (typical of MS/TP devices): a long Object_List does not fit in one answer and must be read by index.
- Protocol_Services_Supported that does not match what the device actually does: trust the answers, not the bits.
- UTC_Offset with the opposite sign: time stamps of trend records and alarms shift by twice the offset.
Reading, writing and watching it in OTDeck
- On connect OTDeck reads the device object: name, vendor, model, firmware, protocol revision, max APDU, segmentation; services and object types supported are shown by name.
- The object tree is Object_List grouped by type with object names, read by index when the whole list does not fit; Detected behaviour lists what OTDeck learnt about the device (no ReadPropertyMultiple, small APDU, no Property_List…).
- Who-Is discovery with an instance range, across a BBMD or through a BACnet router; EDE export of one device or all (Pro).
- The Alarms tab works per device: GetEventInformation lists that device's alarms, and Recipients reads its notification classes.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
What is the range of a BACnet device instance?
0 to 4194302. 4194303 is reserved as the wildcard, used to address 'whatever device this is' in a request.
Where do I find which services a BACnet device supports?
In Protocol_Services_Supported (property 97) of the device object, a bit string with one bit per service.
What is Database_Revision for?
It increases when the device's objects or configuration change, so a BMS knows to read the device again.
Related object types
Download OTDeck, free for one connection BACnet client All object types
Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.