Every BACnet device has exactly one device object. Its instance is the device's address on the BACnet internetwork, and its properties describe who made it, what it supports and which objects it holds.

Object type
8 (device)
Common abbreviation
DEV
Present_Value
None
Commandable
No
COV
No
In OTDeck
device:1 or dev:1

What it is

The device object identifies the controller (device instance 0 to 4194302; 4194303 is the wildcard) and lists its other objects in Object_List. A BMS reads it first, on discovery, and again when Database_Revision changes.

Object type 8 in ASHRAE 135. The device instance must be unique on the whole internetwork, not only on one subnet.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Device object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Object_Identifier75yesdevice,N: N is the device instance used in Who-Is ranges.
Object_Name77yesUnique on the internetwork, like the instance.
System_Status112yesoperational, operational-read-only, download-required, download-in-progress, non-operational, backup-in-progress.
Vendor_Name121yesThe manufacturer as text.
Vendor_Identifier120yesThe manufacturer's number assigned by ASHRAE.
Model_Name70yesThe product.
Firmware_Revision44yesFirmware version.
Application_Software_Version12yesVersion of the application loaded into the controller.
Protocol_Revision139yesWhich revision of BACnet the device implements; Property_List exists from revision 14.
Protocol_Services_Supported97yesA bit string of the services the device executes: ReadPropertyMultiple, SubscribeCOV, ReadRange…
Protocol_Object_Types_Supported96yesA bit string of the object types it can have.
Object_List76yesEvery object in the device; index 0 holds the count, so a long list can be read element by element.
Max_APDU_Length_Accepted62yesThe largest message it takes: 50, 128, 206, 480, 1024 or 1476 bytes.
Segmentation_Supported107yessegmented-both, segmented-transmit, segmented-receive or no-segmentation.
APDU_Timeout11yesMilliseconds the device waits for an answer before retrying.
Number_Of_APDU_Retries73yesHow often it retries.
Database_Revision155yesGoes up when objects are created, deleted or renamed, or the configuration changes: the signal to re-read the device.
UTC_Offset119Minutes between local time and UTC; vendors disagree on the sign.
Daylight_Savings_Status24TRUE while daylight saving time is in effect.

Worked example: What to check in a device object on site

Reading the device object first saves time on every other request. These properties answer the usual questions.

PropertyWhat it tells you
Vendor_Name, Model_Name, Firmware_RevisionWhether the controller is the one on the submittal, and whether the firmware has the fix you were promised.
Protocol_RevisionWhich edition of the standard the device follows: later revisions add objects and properties (network port, BACnet/SC) and date wildcards, so an old revision explains a missing property.
Max_APDU_Length_Accepted1476 on BACnet/IP, often 480 or less for an MS/TP device behind a router. Long ReadPropertyMultiple requests must fit.
Segmentation_Supportedno-segmentation means a large Object_List cannot be read in one go: read Object_List[0] for the count, then index by index.
APDU_Timeout, Number_Of_APDU_RetriesHow long the device waits for confirmations, so your client's timeout matches it on slow MS/TP trunks.
Database_RevisionChanges when objects are added, deleted or renamed: compare it with your last export to know whether the point list changed.
Local_Time, UTC_OffsetWhether schedules and calendars will switch at the right hour.

Commanding

The device object is not commanded. Device-level actions (time synchronisation, reinitialize, communication control) are separate services, not property writes.

COV

The device object reports no COV. Re-read it after a restart or when Database_Revision changes.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

What is the range of a BACnet device instance?

0 to 4194302. 4194303 is reserved as the wildcard, used to address 'whatever device this is' in a request.

Where do I find which services a BACnet device supports?

In Protocol_Services_Supported (property 97) of the device object, a bit string with one bit per service.

What is Database_Revision for?

It increases when the device's objects or configuration change, so a BMS knows to read the device again.

Related object types

Download OTDeck, free for one connection BACnet client All object types

Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.