BACnet object reference · type 15
BACnet Notification Class object (type 15): Recipient_List and alarm priority
The BACnet notification class object decides where alarms go. Every object that reports events names a notification class; the class holds the event priorities, which transitions need acknowledging, and the list of recipients.
- Object type
- 15 (notification-class)
- Common abbreviation
- NC
- Present_Value
- None
- Commandable
- No
- COV
- No
- In OTDeck
- notification-class:1 or nc:1
What it is
Alarms in BACnet are produced by the objects (intrinsic reporting) or by event enrollment objects, and distributed by notification classes: one class for critical alarms, one for maintenance messages, and so on.
Object type 15 in ASHRAE 135. Its Notification_Class number usually equals its instance.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Notification Class object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Notification_Class | 17 | yes | The class number objects refer to. |
| Priority | 86 | yes | Three event priorities (0–255, lower is more urgent): for to-offnormal, to-fault and to-normal notifications. |
| Ack_Required | 1 | yes | Three bits: which of those transitions must be acknowledged by an operator. |
| Recipient_List | 102 | yes | The destinations: valid days, from and to times, the recipient (a device or an address), process identifier, confirmed or unconfirmed, and which transitions. |
Worked example: A Recipient_List read in plain words
notification-class:2, Comfort alarms. Each Recipient_List entry says who is told, when, about which transitions and how.
| Recipient_List entry | Meaning |
|---|---|
| device:1001, every day 00:00-23:59, all transitions, confirmed | The head-end gets every to-offnormal, to-fault and to-normal, and confirms each one. |
| device:1050, Mon-Fri 07:00-18:00, to-offnormal and to-fault, unconfirmed | A service workstation gets new alarms in working hours only. |
| address 192.168.10.44:47808, every day, all transitions, unconfirmed | A laptop by address, often OTDeck added during commissioning: remove it before leaving. |
Priority holds three numbers, for to-offnormal, to-fault and to-normal (0 to 255, lower is more urgent), and Ack_Required says which of the three must be acknowledged.
Commanding
A notification class is configured, not commanded. Recipient_List is written whole, or changed with AddListElement and RemoveListElement on devices that support them.
COV
Notification classes do not report COV. Event notifications go to the recipients in Recipient_List when an object of the class changes event state.
Typical uses in HVAC and BMS
- Separate classes for life safety, critical plant, and maintenance alarms, each with its own recipients.
- Routing alarms to the BMS workstation during the day and to an on-call gateway at night through valid days and times.
Field pitfalls
- A client that is not in Recipient_List receives no event notifications; it has to read alarms with GetEventInformation instead.
- A recipient given by address breaks when that workstation changes IP; a device recipient follows the device.
- Ack_Required set but nobody acknowledges: objects keep the unacknowledged transition and show in every alarm summary.
- Event priority is 0–255 here, not the 1–16 of the priority array.
Reading, writing and watching it in OTDeck
- Select notification-class:N (or nc:N): Notification_Class, Priority, Ack_Required and Recipient_List are read with the other properties.
- The Alarms tab reads GetEventInformation from the device every few seconds, so alarms show whether or not OTDeck is a recipient; notifications the device does send to OTDeck are listed under them. Ack sends AcknowledgeAlarm with the device's time stamp (Pro).
- EDE export includes each object's notification class.
- The simulator's notification-class:1 Boiler alarms has priorities 40, 20 and 200 and requires acknowledgement of every transition.
- Recipients, in the Alarms tab, shows every notification class of a device and its Recipient_List in plain words like the table above.
- Receive notifications here (Pro) adds OTDeck to a Recipient_List through the write guard and the write log and keeps only the entries it added; removing them is free, and a head-end's entries are never touched.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
Why do I not receive BACnet alarms?
Event notifications go only to the destinations in the notification class's Recipient_List, and only for the transitions and times listed there. A client not in the list must poll with GetEventInformation or GetAlarmSummary.
What does Ack_Required mean in BACnet?
Three bits, one per transition (to-offnormal, to-fault, to-normal). A transition with its bit set waits for an AcknowledgeAlarm from an operator.