BACnet Analog Input object (AI, type 0)

The BACnet analog input object is a measured value: a temperature sensor, a pressure transmitter, a flow meter. Its Present_Value is a REAL in the engineering units of its Units property, and a client reads it, watches it with COV, or alarms on it with high and low limits.

Object type
0 (analog-input)
Common abbreviation
AI
Present_Value
REAL (32-bit float), in the units of Units
Commandable
No; Present_Value is writable only while Out_Of_Service is TRUE
COV
Yes: on a change of at least COV_Increment, or of Status_Flags
In OTDeck
analog-input:1 or ai:1

What it is

An analog input stands for a physical analog input of the controller: the value the device measured, after its own scaling. Clients do not command it; the hardware sets Present_Value.

Object type 0 in ASHRAE 135. Its identifier is written analog-input,N (or AI-N in many BMS tools), with N the instance within the device.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Analog Input object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Present_Value85yesThe measured value as REAL, already scaled to Units by the device.
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Event_State36yesnormal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault).
Reliability103Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well.
Out_Of_Service81yesTRUE decouples Present_Value from the sensor: the value freezes, can be written (for tests and overrides), and the out-of-service flag is set.
Units117yesAn enumeration, not text: 62 is degrees-Celsius, 64 degrees-Fahrenheit, 98 percent, 29 percent-relative-humidity, 54 kilopascals, 95 no-units.
Min_Pres_Value69The lowest value the input can report; often the sensor range.
Max_Pres_Value65The highest value the input can report.
Resolution106The smallest change the input can resolve.
COV_Increment22if COVThe smallest change of Present_Value that makes the device send a COV notification.
High_Limit45Above this (for Time_Delay) the object goes to high-limit, when the high limit is enabled in Limit_Enable.
Low_Limit59Below this the object goes to low-limit.
Deadband25How far back inside the limits the value must come before the object returns to normal.
Limit_Enable52Two bits: low-limit enable and high-limit enable.
Time_Delay113Seconds a condition must last before the event state changes.
Notification_Class17The notification-class object whose priorities, acknowledgement rules and recipients this object's alarms use.
Event_Enable35Which transitions (to-offnormal, to-fault, to-normal) are reported.

Commanding

An analog input has no priority array and no Relinquish_Default: there is nothing to command. The standard makes Present_Value writable only while Out_Of_Service is TRUE, and the value then stays as written until Out_Of_Service goes back to FALSE.

A device answers a write to an in-service input with an error (usually write-access-denied). To feed a test value into control logic, set Out_Of_Service first, which needs a tool that writes that property.

COV

A COV subscription to an analog input sends a notification when Present_Value has moved by at least COV_Increment since the last notification, and whenever Status_Flags change. A COV_Increment of 0.1 on a °C point means a notification for every tenth of a degree.

Too small an increment floods the network with notifications on a noisy sensor; too large a one makes a slowly drifting value look frozen.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

Can you write the Present_Value of a BACnet analog input?

Only while Out_Of_Service is TRUE. In service, the value comes from the sensor and the device refuses the write; out of service, the written value stays until the object is put back in service.

What does COV_Increment do on an analog input?

It is the smallest change of Present_Value that triggers a COV notification to subscribers. A change of Status_Flags always triggers one, whatever the increment.

What is the difference between an analog input and an analog value?

An analog input is a hardware measurement and is not commandable. An analog value is a software value inside the controller (a setpoint, a calculated value) and may be commandable with a priority array.