BACnet object reference · type 0
BACnet Analog Input object (AI, type 0)
The BACnet analog input object is a measured value: a temperature sensor, a pressure transmitter, a flow meter. Its Present_Value is a REAL in the engineering units of its Units property, and a client reads it, watches it with COV, or alarms on it with high and low limits.
- Object type
- 0 (analog-input)
- Common abbreviation
- AI
- Present_Value
- REAL (32-bit float), in the units of Units
- Commandable
- No; Present_Value is writable only while Out_Of_Service is TRUE
- COV
- Yes: on a change of at least COV_Increment, or of Status_Flags
- In OTDeck
- analog-input:1 or ai:1
What it is
An analog input stands for a physical analog input of the controller: the value the device measured, after its own scaling. Clients do not command it; the hardware sets Present_Value.
Object type 0 in ASHRAE 135. Its identifier is written analog-input,N (or AI-N in many BMS tools), with N the instance within the device.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Analog Input object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Present_Value | 85 | yes | The measured value as REAL, already scaled to Units by the device. |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Event_State | 36 | yes | normal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault). |
| Reliability | 103 | Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well. | |
| Out_Of_Service | 81 | yes | TRUE decouples Present_Value from the sensor: the value freezes, can be written (for tests and overrides), and the out-of-service flag is set. |
| Units | 117 | yes | An enumeration, not text: 62 is degrees-Celsius, 64 degrees-Fahrenheit, 98 percent, 29 percent-relative-humidity, 54 kilopascals, 95 no-units. |
| Min_Pres_Value | 69 | The lowest value the input can report; often the sensor range. | |
| Max_Pres_Value | 65 | The highest value the input can report. | |
| Resolution | 106 | The smallest change the input can resolve. | |
| COV_Increment | 22 | if COV | The smallest change of Present_Value that makes the device send a COV notification. |
| High_Limit | 45 | Above this (for Time_Delay) the object goes to high-limit, when the high limit is enabled in Limit_Enable. | |
| Low_Limit | 59 | Below this the object goes to low-limit. | |
| Deadband | 25 | How far back inside the limits the value must come before the object returns to normal. | |
| Limit_Enable | 52 | Two bits: low-limit enable and high-limit enable. | |
| Time_Delay | 113 | Seconds a condition must last before the event state changes. | |
| Notification_Class | 17 | The notification-class object whose priorities, acknowledgement rules and recipients this object's alarms use. | |
| Event_Enable | 35 | Which transitions (to-offnormal, to-fault, to-normal) are reported. |
Commanding
An analog input has no priority array and no Relinquish_Default: there is nothing to command. The standard makes Present_Value writable only while Out_Of_Service is TRUE, and the value then stays as written until Out_Of_Service goes back to FALSE.
A device answers a write to an in-service input with an error (usually write-access-denied). To feed a test value into control logic, set Out_Of_Service first, which needs a tool that writes that property.
COV
A COV subscription to an analog input sends a notification when Present_Value has moved by at least COV_Increment since the last notification, and whenever Status_Flags change. A COV_Increment of 0.1 on a °C point means a notification for every tenth of a degree.
Too small an increment floods the network with notifications on a noisy sensor; too large a one makes a slowly drifting value look frozen.
Typical uses in HVAC and BMS
- Supply and return water temperatures, outdoor air, zone temperature.
- Duct static pressure, differential pressure across a filter or pump, building pressure.
- Humidity, CO2, airflow, valve and damper position feedback.
- Energy meter readings exposed by gateways, often as AI with kW or kWh units.
Field pitfalls
- Out_Of_Service left TRUE after commissioning: the value never changes again while the plant does. The out-of-service status flag gives it away.
- Units read as a number: 62 is °C, 64 is °F. A gateway that reports Fahrenheit under the Celsius code (or the other way) produces plausible but wrong numbers.
- Reliability not no-fault-detected (no-sensor, open-loop, over-range): the value is a placeholder, not a reading. Check Status_Flags fault before trusting it.
- COV_Increment 0 or absent: some devices then notify on every sample; others do not support COV on the object at all.
Reading, writing and watching it in OTDeck
- Select analog-input:1 (or type ai:1) in the object tree: OTDeck reads every property the device lists (Property_List, or the standard set on older devices) with ReadPropertyMultiple, and shows Present_Value large with its units and status flags.
- Watch it: the watch list subscribes with SubscribeCOV (lifetime 300 s, renewed while watched) and falls back to polling when the device refuses; the value goes to the trend panel next to MQTT, Modbus and OPC UA values.
- Alarms from High_Limit and Low_Limit show in the Alarms tab (GetEventInformation) with their transitions; Ack acknowledges one (Pro).
- The built-in simulator's analog-input:1 Supply temperature has COV_Increment 0.1 and a HighTemperature alarm above 90 °C: raise the setpoint to 95 and watch it trip.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
Can you write the Present_Value of a BACnet analog input?
Only while Out_Of_Service is TRUE. In service, the value comes from the sensor and the device refuses the write; out of service, the written value stays until the object is put back in service.
What does COV_Increment do on an analog input?
It is the smallest change of Present_Value that triggers a COV notification to subscribers. A change of Status_Flags always triggers one, whatever the increment.
What is the difference between an analog input and an analog value?
An analog input is a hardware measurement and is not commandable. An analog value is a software value inside the controller (a setpoint, a calculated value) and may be commandable with a priority array.