BACnet object reference · type 2
BACnet Analog Value object (AV, type 2)
The BACnet analog value object is a number that lives in the controller's software rather than at a terminal: a setpoint, a calculated value, a parameter. It may be commandable with a priority array, or a plain writable value.
- Object type
- 2 (analog-value)
- Common abbreviation
- AV
- Present_Value
- REAL, in the units of Units
- Commandable
- Optional: commandable only when it has Priority_Array and Relinquish_Default
- COV
- Yes: on a change of at least COV_Increment, or of Status_Flags
- In OTDeck
- analog-value:1 or av:1
What it is
An analog value holds a control-program number: a room setpoint, a reset schedule parameter, a calculated enthalpy, a value received from another system. No hardware is behind it.
Object type 2 in ASHRAE 135, written analog-value,N or AV-N. The device decides whether a given AV is commandable; the presence of Priority_Array tells you.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Analog Value object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Present_Value | 85 | yes | The value as REAL. On a commandable AV, the winner of the priority array. |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Event_State | 36 | yes | normal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault). |
| Reliability | 103 | Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well. | |
| Out_Of_Service | 81 | yes | TRUE takes the value out of the control program's hands; it can then be set for testing. |
| Units | 117 | yes | An enumeration, not text: 62 is degrees-Celsius, 64 degrees-Fahrenheit, 98 percent, 29 percent-relative-humidity, 54 kilopascals, 95 no-units. |
| Priority_Array | 87 | if commandable | 16 slots, 1 highest. Each holds a commanded value or NULL; the highest non-NULL slot becomes Present_Value. |
| Relinquish_Default | 104 | if commandable | The value Present_Value takes when all 16 slots are NULL. |
| COV_Increment | 22 | if COV | The smallest change of Present_Value that makes the device send a COV notification. |
| High_Limit | 45 | Upper alarm limit for out-of-range reporting. | |
| Low_Limit | 59 | Lower alarm limit. | |
| Deadband | 25 | Hysteresis on the way back to normal. | |
| Notification_Class | 17 | The notification-class object whose priorities, acknowledgement rules and recipients this object's alarms use. |
Worked example: A setpoint with COV and an alarm
analog-value:3, a room setpoint in degrees Celsius, with intrinsic reporting.
| Property | Value and effect |
|---|---|
| Present_Value | 21.0, written by the room unit at priority 16. |
| COV_Increment | 0.5: a change to 21.3 sends no COV notification; 21.6 does. |
| High_Limit, Low_Limit | 26.0 and 16.0, with Limit_Enable set for both. |
| Deadband | 0.5: after a high-limit alarm the value must fall below 25.5 to return to normal. |
| Time_Delay | 60 s: a spike shorter than a minute raises no alarm. |
| Event_Enable, Notification_Class | to-offnormal and to-normal; class 2, Comfort alarms. |
A COV_Increment of 0 floods every subscriber with a notification per tiny change; a large one makes trends look stepped. 0.1 to 0.5 °C is typical for room values.
Priority array and relinquish
A write to Present_Value goes into one slot of the priority array: the priority in the WriteProperty request, or 16 when the request carries none. The analog value takes the value of the highest-priority slot that is not NULL. Writing NULL at a priority (relinquish) empties that slot; when all 16 are empty, Present_Value falls back to Relinquish_Default.
A non-commandable AV has no priority array: a write simply replaces the value, the last writer wins, and a priority in the request has no effect. Some devices make such values read-only and answer write-access-denied.
| Priority | Use in ASHRAE 135 |
|---|---|
| 1 | Manual-Life Safety |
| 2 | Automatic-Life Safety |
| 3 | Available |
| 4 | Available |
| 5 | Critical Equipment Control |
| 6 | Minimum On/Off |
| 7 | Available |
| 8 | Manual Operator |
| 9–16 | Available (16 is used when a write carries no priority) |
COV
COV notifications follow COV_Increment and Status_Flags, as on analog inputs. A setpoint that rarely changes is cheap to watch with COV.
Typical uses in HVAC and BMS
- Zone, supply air and hot water setpoints the BMS or an operator adjusts.
- Occupied and unoccupied setpoints, reset curve parameters, PID tuning values exposed by the vendor.
- Calculated values: mixed air temperature, efficiency, a value written in from another controller.
Field pitfalls
- Assuming every AV is commandable: without Priority_Array a write at priority 8 just overwrites the value, and a relinquish has nothing to release.
- The same setpoint written by the BMS at 16 and by an operator at 8: the operator's value stays until relinquished, and the BMS reports it as overridden.
- Vendors that store AV writes in flash: frequent writes from a script wear the memory. Check the vendor's notes before writing in a loop.
- Limits set but Limit_Enable or Event_Enable empty: the limits are there, the alarm never comes. OTDeck's Configured view shows both side by side.
Reading, writing and watching it in OTDeck
- Select analog-value:1 (or av:1) in the object tree: OTDeck reads every property the device lists (Property_List, or the standard set on older devices) with ReadPropertyMultiple, and shows Present_Value large with its units and status flags.
- Watch it: the watch list subscribes with SubscribeCOV (lifetime 300 s, renewed while watched) and falls back to polling when the device refuses; the value goes to the trend panel next to MQTT, Modbus and OPC UA values.
- A commandable AV shows its priority array with Relinquish per slot; a non-commandable one is written without a priority, as the write dialog says. Writes are Pro, refused on read-only connections, need the connection name typed on production connections, and land in the write log as bacnet.write with the object, value and priority.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
Is a BACnet analog value commandable?
It can be. A commandable analog value has Priority_Array and Relinquish_Default; one without them is a plain value that a write simply replaces.
What is the difference between an analog value and an analog output?
An analog output drives a physical output and is always commandable. An analog value is a software value (a setpoint, a calculated number) and is commandable only if the device gives it a priority array.
Related object types
Download OTDeck, free for one connection BACnet client All object types
Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.