OTDeck

BACnet object reference · type 2

BACnet Analog Value object (AV, type 2)

The BACnet analog value object is a number that lives in the controller's software rather than at a terminal: a setpoint, a calculated value, a parameter. It may be commandable with a priority array, or a plain writable value.

Object type
2 (analog-value)
Common abbreviation
AV
Present_Value
REAL, in the units of Units
Commandable
Optional: commandable only when it has Priority_Array and Relinquish_Default
COV
Yes: on a change of at least COV_Increment, or of Status_Flags
In OTDeck
analog-value:1 or av:1

What it is

An analog value holds a control-program number: a room setpoint, a reset schedule parameter, a calculated enthalpy, a value received from another system. No hardware is behind it.

Object type 2 in ASHRAE 135, written analog-value,N or AV-N. The device decides whether a given AV is commandable; the presence of Priority_Array tells you.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Analog Value object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Present_Value85yesThe value as REAL. On a commandable AV, the winner of the priority array.
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Event_State36yesnormal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault).
Reliability103Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well.
Out_Of_Service81yesTRUE takes the value out of the control program's hands; it can then be set for testing.
Units117yesAn enumeration, not text: 62 is degrees-Celsius, 64 degrees-Fahrenheit, 98 percent, 29 percent-relative-humidity, 54 kilopascals, 95 no-units.
Priority_Array87if commandable16 slots, 1 highest. Each holds a commanded value or NULL; the highest non-NULL slot becomes Present_Value.
Relinquish_Default104if commandableThe value Present_Value takes when all 16 slots are NULL.
COV_Increment22if COVThe smallest change of Present_Value that makes the device send a COV notification.
High_Limit45Upper alarm limit for out-of-range reporting.
Low_Limit59Lower alarm limit.
Deadband25Hysteresis on the way back to normal.
Notification_Class17The notification-class object whose priorities, acknowledgement rules and recipients this object's alarms use.

Worked example: A setpoint with COV and an alarm

analog-value:3, a room setpoint in degrees Celsius, with intrinsic reporting.

PropertyValue and effect
Present_Value21.0, written by the room unit at priority 16.
COV_Increment0.5: a change to 21.3 sends no COV notification; 21.6 does.
High_Limit, Low_Limit26.0 and 16.0, with Limit_Enable set for both.
Deadband0.5: after a high-limit alarm the value must fall below 25.5 to return to normal.
Time_Delay60 s: a spike shorter than a minute raises no alarm.
Event_Enable, Notification_Classto-offnormal and to-normal; class 2, Comfort alarms.

A COV_Increment of 0 floods every subscriber with a notification per tiny change; a large one makes trends look stepped. 0.1 to 0.5 °C is typical for room values.

Priority array and relinquish

A write to Present_Value goes into one slot of the priority array: the priority in the WriteProperty request, or 16 when the request carries none. The analog value takes the value of the highest-priority slot that is not NULL. Writing NULL at a priority (relinquish) empties that slot; when all 16 are empty, Present_Value falls back to Relinquish_Default.

A non-commandable AV has no priority array: a write simply replaces the value, the last writer wins, and a priority in the request has no effect. Some devices make such values read-only and answer write-access-denied.

PriorityUse in ASHRAE 135
1Manual-Life Safety
2Automatic-Life Safety
3Available
4Available
5Critical Equipment Control
6Minimum On/Off
7Available
8Manual Operator
9–16Available (16 is used when a write carries no priority)

COV

COV notifications follow COV_Increment and Status_Flags, as on analog inputs. A setpoint that rarely changes is cheap to watch with COV.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

Is a BACnet analog value commandable?

It can be. A commandable analog value has Priority_Array and Relinquish_Default; one without them is a plain value that a write simply replaces.

What is the difference between an analog value and an analog output?

An analog output drives a physical output and is always commandable. An analog value is a software value (a setpoint, a calculated number) and is commandable only if the device gives it a priority array.

Related object types