BACnet object reference · type 17

BACnet Schedule object (type 17): weekly schedule and exceptions

The BACnet schedule object switches values by the clock: occupancy on at 07:00, off at 18:00, a different week for holidays. Its weekly schedule and exceptions decide Present_Value, which the schedule writes to the objects in its target list.

Object type
17 (schedule)
Common abbreviation
SCH
Present_Value
Any primitive datatype, the same for every entry and target (often Enumerated active/inactive, REAL or Unsigned)
Commandable
No; it commands other objects at Priority_For_Writing
COV
Device-dependent; most clients read it or watch its targets
In OTDeck
schedule:1

What it is

A schedule holds a week of time-value pairs and a list of exceptions. At every moment its Present_Value is the value of the highest-priority exception in effect, else the weekly schedule's value, else Schedule_Default. When Present_Value changes, the schedule writes it to each property in List_Of_Object_Property_References at Priority_For_Writing.

Object type 17 in ASHRAE 135.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Schedule object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Present_Value85yesThe value in effect now. Its datatype is the schedule's datatype.
Effective_Period32yesThe date range in which the schedule acts at all; outside it the schedule writes nothing.
Weekly_Schedule123An array of 7 daily schedules, index 1 = Monday to 7 = Sunday; each a list of time-value pairs. A value holds from its time until the next entry.
Exception_Schedule38A list of special events: a period (a date, a date range, a week-and-day pattern or a calendar object), their own time-values and an event priority 1 (highest) to 16.
Schedule_Default174yesThe value when no weekly entry or exception applies, or when an entry is NULL.
List_Of_Object_Property_References54yesThe targets: object and property (usually Present_Value) the schedule writes.
Priority_For_Writing88yesThe priority 1–16 the schedule writes its targets at.
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Reliability103yesWhy a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well.
Out_Of_Service81yesTRUE stops the schedule from evaluating and writing; Present_Value can then be written.

Commanding

The schedule itself is not commanded; it is a commander. It writes its targets at Priority_For_Writing, so a command at a higher priority (an operator at 8, say) outranks the schedule until it is relinquished.

Within the schedule, exceptions outrank the weekly schedule, and among exceptions event priority 1 is the highest. A NULL value in an entry hands over to the next lower layer: an exception's NULL lets the weekly schedule apply again; a weekly NULL leads to Schedule_Default.

COV

Watch the targets rather than the schedule: a COV subscription to the binary value or setpoint the schedule writes shows every switch.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

How does the BACnet weekly schedule work?

Weekly_Schedule is an array of 7 days, Monday first. Each day is a list of time-value pairs; each value holds from its time until the next entry of that day.

What overrides a BACnet weekly schedule?

Inside the schedule, any exception in Exception_Schedule that applies today, the one with the highest event priority (1) first. Outside it, any command on the target at a priority higher than the schedule's Priority_For_Writing.

What is Schedule_Default?

The value of the schedule when no weekly entry or exception gives one, or when the entry in effect is NULL.

Related object types