BACnet Binary Value object (BV, type 5)

The BACnet binary value object is an on/off value inside the controller: an enable, an occupancy flag, a mode switch, an alarm reset. It may be commandable with a priority array.

Object type
5 (binary-value)
Common abbreviation
BV
Present_Value
BACnetBinaryPV: inactive (0) or active (1)
Commandable
Optional: commandable only when it has Priority_Array and Relinquish_Default
COV
Yes: on every change of Present_Value or Status_Flags
In OTDeck
binary-value:1 or bv:1

What it is

A binary value is a software point with two states. Schedules write occupancy to binary values; BMS front ends write system enables to them.

Object type 5 in ASHRAE 135, written binary-value,N or BV-N. Unlike inputs and outputs it has no Polarity.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Binary Value object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Present_Value85yesactive or inactive.
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Event_State36yesnormal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault).
Reliability103Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well.
Out_Of_Service81yesTRUE takes the value away from the program that sets it.
Priority_Array87if commandable16 slots, 1 highest. Each holds a commanded value or NULL; the highest non-NULL slot becomes Present_Value.
Relinquish_Default104if commandableThe value Present_Value takes when all 16 slots are NULL.
Active_Text4What active means on site: Run, Open, Occupied, Alarm.
Inactive_Text46What inactive means: Stop, Closed, Unoccupied, Normal.
Alarm_Value6The state that counts as offnormal for a change-of-state alarm.
Elapsed_Active_Time33Seconds spent active since the last reset: run hours of a fan or pump.
Change_Of_State_Count15How many times the value changed since the last reset: starts of a motor.

Priority array and relinquish

A write to Present_Value goes into one slot of the priority array: the priority in the WriteProperty request, or 16 when the request carries none. The binary value takes the value of the highest-priority slot that is not NULL. Writing NULL at a priority (relinquish) empties that slot; when all 16 are empty, Present_Value falls back to Relinquish_Default.

A non-commandable BV has no priority array: a write replaces the value, last writer wins.

PriorityUse in ASHRAE 135
1Manual-Life Safety
2Automatic-Life Safety
3Available
4Available
5Critical Equipment Control
6Minimum On/Off
7Available
8Manual Operator
9–16Available (16 is used when a write carries no priority)

COV

Every change of Present_Value or Status_Flags is reported, as on binary inputs and outputs.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

What is a BACnet binary value used for?

Software on/off points: enables, occupancy, modes and resets that live in the controller's program rather than on a terminal.

Does a BACnet binary value have a priority array?

Only if it is commandable. A commandable binary value has Priority_Array and Relinquish_Default and behaves like a binary output; otherwise a write replaces the value.