BACnet object reference · type 5
BACnet Binary Value object (BV, type 5)
The BACnet binary value object is an on/off value inside the controller: an enable, an occupancy flag, a mode switch, an alarm reset. It may be commandable with a priority array.
- Object type
- 5 (binary-value)
- Common abbreviation
- BV
- Present_Value
- BACnetBinaryPV: inactive (0) or active (1)
- Commandable
- Optional: commandable only when it has Priority_Array and Relinquish_Default
- COV
- Yes: on every change of Present_Value or Status_Flags
- In OTDeck
- binary-value:1 or bv:1
What it is
A binary value is a software point with two states. Schedules write occupancy to binary values; BMS front ends write system enables to them.
Object type 5 in ASHRAE 135, written binary-value,N or BV-N. Unlike inputs and outputs it has no Polarity.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Binary Value object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Present_Value | 85 | yes | active or inactive. |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Event_State | 36 | yes | normal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault). |
| Reliability | 103 | Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well. | |
| Out_Of_Service | 81 | yes | TRUE takes the value away from the program that sets it. |
| Priority_Array | 87 | if commandable | 16 slots, 1 highest. Each holds a commanded value or NULL; the highest non-NULL slot becomes Present_Value. |
| Relinquish_Default | 104 | if commandable | The value Present_Value takes when all 16 slots are NULL. |
| Active_Text | 4 | What active means on site: Run, Open, Occupied, Alarm. | |
| Inactive_Text | 46 | What inactive means: Stop, Closed, Unoccupied, Normal. | |
| Alarm_Value | 6 | The state that counts as offnormal for a change-of-state alarm. | |
| Elapsed_Active_Time | 33 | Seconds spent active since the last reset: run hours of a fan or pump. | |
| Change_Of_State_Count | 15 | How many times the value changed since the last reset: starts of a motor. |
Priority array and relinquish
A write to Present_Value goes into one slot of the priority array: the priority in the WriteProperty request, or 16 when the request carries none. The binary value takes the value of the highest-priority slot that is not NULL. Writing NULL at a priority (relinquish) empties that slot; when all 16 are empty, Present_Value falls back to Relinquish_Default.
A non-commandable BV has no priority array: a write replaces the value, last writer wins.
| Priority | Use in ASHRAE 135 |
|---|---|
| 1 | Manual-Life Safety |
| 2 | Automatic-Life Safety |
| 3 | Available |
| 4 | Available |
| 5 | Critical Equipment Control |
| 6 | Minimum On/Off |
| 7 | Available |
| 8 | Manual Operator |
| 9–16 | Available (16 is used when a write carries no priority) |
COV
Every change of Present_Value or Status_Flags is reported, as on binary inputs and outputs.
Typical uses in HVAC and BMS
- System enables (boiler enable, AHU enable), seasonal mode changeover.
- Occupancy written by a schedule object at its Priority_For_Writing.
- Alarm reset and override request points exposed to the BMS.
Field pitfalls
- A schedule and an operator both command the BV: the operator's value at 8 hides the schedule at 16 until relinquished.
- Assuming every BV is commandable: without Priority_Array a priority in the write has no effect.
- Momentary reset points: some devices set the BV back to inactive by themselves, so a later read does not show the write.
Reading, writing and watching it in OTDeck
- Select binary-value:1 (or bv:1) in the object tree: OTDeck reads every property the device lists (Property_List, or the standard set on older devices) with ReadPropertyMultiple, and shows Present_Value large with its units and status flags.
- Watch it: the watch list subscribes with SubscribeCOV (lifetime 300 s, renewed while watched) and falls back to polling when the device refuses; the value goes to the trend panel next to MQTT, Modbus and OPC UA values.
- Write… takes active / inactive (or on/off, 1/0); a commandable BV shows its priority array with Relinquish per slot. Writes are Pro, refused on read-only connections, need the connection name typed on production connections, and land in the write log as bacnet.write with the object, value and priority.
- The simulator has binary-value:1 Enable (Enabled / Disabled) and binary-value:2 Occupancy, which schedule:1 commands at priority 16.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
What is a BACnet binary value used for?
Software on/off points: enables, occupancy, modes and resets that live in the controller's program rather than on a terminal.
Does a BACnet binary value have a priority array?
Only if it is commandable. A commandable binary value has Priority_Array and Relinquish_Default and behaves like a binary output; otherwise a write replaces the value.
Related object types
Download OTDeck, free for one connection BACnet client All object types
Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.