BACnet Binary Input object (BI, type 3)

The BACnet binary input object is a two-state physical input: a status contact, a flow switch, a filter alarm. Its Present_Value is active or inactive, named on site by Active_Text and Inactive_Text.

Object type
3 (binary-input)
Common abbreviation
BI
Present_Value
BACnetBinaryPV, an enumeration: inactive (0) or active (1)
Commandable
No; Present_Value is writable only while Out_Of_Service is TRUE
COV
Yes: on every change of Present_Value or Status_Flags
In OTDeck
binary-input:1 or bi:1

What it is

A binary input stands for a dry contact or digital input of the controller. Polarity decides whether a closed contact reads active or inactive.

Object type 3 in ASHRAE 135, written binary-input,N or BI-N.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Binary Input object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Present_Value85yesactive or inactive (an Enumerated, not a Boolean).
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Event_State36yesnormal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault).
Reliability103Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well.
Out_Of_Service81yesTRUE decouples the value from the contact so it can be written for testing.
Polarity84yesnormal or reverse. Reverse inverts the relation between the physical contact and Present_Value.
Active_Text4What active means on site: Run, Open, Occupied, Alarm.
Inactive_Text46What inactive means: Stop, Closed, Unoccupied, Normal.
Change_Of_State_Count15How many times the value changed since the last reset: starts of a motor.
Elapsed_Active_Time33Seconds spent active since the last reset: run hours of a fan or pump.
Alarm_Value6The value that is offnormal (change-of-state alarm): active for a filter-dirty contact, for example.
Time_Delay113Seconds a condition must last before the event state changes.
Notification_Class17The notification-class object whose priorities, acknowledgement rules and recipients this object's alarms use.

Commanding

A binary input has no priority array. As with an analog input, the standard lets a client write Present_Value only while Out_Of_Service is TRUE.

COV

Every change of Present_Value is a change of value: no increment applies. A notification is also sent when Status_Flags change.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

What data type is a BACnet binary Present_Value?

BACnetBinaryPV, an enumeration with inactive = 0 and active = 1. It is encoded as Enumerated, not as a Boolean.

What does Polarity do on a binary input?

With normal polarity an energised input reads active; with reverse polarity it reads inactive. It inverts the meaning of the contact, not the encoding.