BACnet Binary Input object (BI, type 3)
The BACnet binary input object is a two-state physical input: a status contact, a flow switch, a filter alarm. Its Present_Value is active or inactive, named on site by Active_Text and Inactive_Text.
- Object type
- 3 (binary-input)
- Common abbreviation
- BI
- Present_Value
- BACnetBinaryPV, an enumeration: inactive (0) or active (1)
- Commandable
- No; Present_Value is writable only while Out_Of_Service is TRUE
- COV
- Yes: on every change of Present_Value or Status_Flags
- In OTDeck
- binary-input:1 or bi:1
What it is
A binary input stands for a dry contact or digital input of the controller. Polarity decides whether a closed contact reads active or inactive.
Object type 3 in ASHRAE 135, written binary-input,N or BI-N.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Binary Input object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Present_Value | 85 | yes | active or inactive (an Enumerated, not a Boolean). |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Event_State | 36 | yes | normal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault). |
| Reliability | 103 | Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well. | |
| Out_Of_Service | 81 | yes | TRUE decouples the value from the contact so it can be written for testing. |
| Polarity | 84 | yes | normal or reverse. Reverse inverts the relation between the physical contact and Present_Value. |
| Active_Text | 4 | What active means on site: Run, Open, Occupied, Alarm. | |
| Inactive_Text | 46 | What inactive means: Stop, Closed, Unoccupied, Normal. | |
| Change_Of_State_Count | 15 | How many times the value changed since the last reset: starts of a motor. | |
| Elapsed_Active_Time | 33 | Seconds spent active since the last reset: run hours of a fan or pump. | |
| Alarm_Value | 6 | The value that is offnormal (change-of-state alarm): active for a filter-dirty contact, for example. | |
| Time_Delay | 113 | Seconds a condition must last before the event state changes. | |
| Notification_Class | 17 | The notification-class object whose priorities, acknowledgement rules and recipients this object's alarms use. |
Commanding
A binary input has no priority array. As with an analog input, the standard lets a client write Present_Value only while Out_Of_Service is TRUE.
COV
Every change of Present_Value is a change of value: no increment applies. A notification is also sent when Status_Flags change.
Typical uses in HVAC and BMS
- Fan and pump status (run feedback from a current switch or auxiliary contact).
- Filter differential pressure switches, freeze stats, flow switches, smoke detector relays.
- Door contacts, occupancy sensors, alarm contacts from packaged equipment.
Field pitfalls
- Polarity reverse set by mistake: the display says Running while the pump is off. Compare against the equipment, not only the screen.
- Writing true or 1 as a Boolean: Present_Value is an Enumerated; many devices answer invalid-data-type to a Boolean.
- Active_Text missing or generic (Active / Inactive): check what active means on that point before writing an alarm rule.
- Chattering contacts flood COV subscribers; Time_Delay on the alarm side does not throttle COV.
Reading, writing and watching it in OTDeck
- Select binary-input:1 (or bi:1) in the object tree: OTDeck reads every property the device lists (Property_List, or the standard set on older devices) with ReadPropertyMultiple, and shows Present_Value large with its units and status flags.
- Watch it: the watch list subscribes with SubscribeCOV (lifetime 300 s, renewed while watched) and falls back to polling when the device refuses; the value goes to the trend panel next to MQTT, Modbus and OPC UA values.
- Values show as active or inactive; the object panel lists Active_Text and Inactive_Text with the other properties.
- The simulator's binary-input:1 Pump running (Running / Stopped) is a feedback contact to watch.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
What data type is a BACnet binary Present_Value?
BACnetBinaryPV, an enumeration with inactive = 0 and active = 1. It is encoded as Enumerated, not as a Boolean.
What does Polarity do on a binary input?
With normal polarity an energised input reads active; with reverse polarity it reads inactive. It inverts the meaning of the contact, not the encoding.