BACnet object reference · type 13
BACnet Multi-state Input object (MSI, type 13)
The BACnet multi-state input object reports one of several states: the mode of a packaged unit, the stage of a compressor, a selector switch. Present_Value is a number from 1 to Number_Of_States, named by State_Text.
- Object type
- 13 (multi-state-input)
- Common abbreviation
- MSI
- Present_Value
- Unsigned, 1 to Number_Of_States (never 0)
- Commandable
- No; Present_Value is writable only while Out_Of_Service is TRUE
- COV
- Yes: on every change of Present_Value or Status_Flags
- In OTDeck
- multi-state-input:1 or msi:1
What it is
A multi-state input stands for a value with a fixed set of states that the device determines: often the result of decoding several contacts, or a state reported by equipment through an integration.
Object type 13 in ASHRAE 135, written multi-state-input,N or MI-N / MSI-N.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Multi-state Input object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Present_Value | 85 | yes | The state number, 1 to Number_Of_States. |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Event_State | 36 | yes | normal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault). |
| Reliability | 103 | Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well. | |
| Out_Of_Service | 81 | yes | TRUE decouples the value from its source so it can be written for testing. |
| Number_Of_States | 74 | yes | How many states there are; Present_Value runs from 1 to this number. |
| State_Text | 110 | An array with one name per state: State_Text[2] is the name of state 2. | |
| Alarm_Values | 7 | The states that count as offnormal (change-of-state alarm). | |
| Fault_Values | 39 | The states that mean a fault: Reliability becomes multi-state-fault. | |
| Notification_Class | 17 | The notification-class object whose priorities, acknowledgement rules and recipients this object's alarms use. |
Commanding
A multi-state input has no priority array. Its Present_Value is writable only while Out_Of_Service is TRUE.
COV
Every change of state is reported, and every change of Status_Flags. No increment applies.
Typical uses in HVAC and BMS
- Unit operating mode (off, heat, cool, fan only) from a rooftop unit.
- Hand-off-auto selector switch position.
- Compressor or burner stage, drive status codes mapped to states.
Field pitfalls
- Off-by-one: states start at 1. Gateways that map a 0-based register to an MSI shift every state by one.
- State_Text missing: the value is a bare number, and its meaning sits in the vendor's points list.
- Number_Of_States changed by a program update while the BMS graphics still assume the old list.
Reading, writing and watching it in OTDeck
- Select multi-state-input:1 (or msi:1) in the object tree: OTDeck reads every property the device lists (Property_List, or the standard set on older devices) with ReadPropertyMultiple, and shows Present_Value large with its units and status flags.
- Watch it: the watch list subscribes with SubscribeCOV (lifetime 300 s, renewed while watched) and falls back to polling when the device refuses; the value goes to the trend panel next to MQTT, Modbus and OPC UA values.
- Values show with their state text, as Auto (2); State_Text and Number_Of_States are in the property table.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
Can a BACnet multi-state value be 0?
No. Present_Value runs from 1 to Number_Of_States; a write of 0 or more than Number_Of_States is refused with value-out-of-range.
Where are the state names of a BACnet multi-state object?
In State_Text, an array with one string per state: State_Text[1] names state 1. It is optional, so some devices only give numbers.
Related object types
Download OTDeck, free for one connection BACnet client All object types