OTDeck

BACnet object reference · type 14

BACnet Multi-state Output object (MSO, type 14)

The BACnet multi-state output object commands one of several states: fan speed low/medium/high, a unit's mode, a staged output. It is always commandable, with the same 16-slot priority array as analog and binary outputs.

Object type
14 (multi-state-output)
Common abbreviation
MSO
Present_Value
Unsigned, 1 to Number_Of_States
Commandable
Always: Priority_Array and Relinquish_Default are required
COV
Yes: on every change of Present_Value or Status_Flags
In OTDeck
multi-state-output:1 or mso:1

What it is

A multi-state output drives equipment with several discrete states, often through several relays or a mode input of a packaged unit.

Object type 14 in ASHRAE 135, written multi-state-output,N or MO-N / MSO-N.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Multi-state Output object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Present_Value85yesThe commanded state, 1 to Number_Of_States.
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Event_State36yesnormal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault).
Reliability103Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well.
Out_Of_Service81yesTRUE disconnects the physical outputs from Present_Value.
Number_Of_States74yesHow many states there are; Present_Value runs from 1 to this number.
State_Text110An array with one name per state: State_Text[2] is the name of state 2.
Priority_Array87yes16 slots, 1 highest. Each holds a commanded value or NULL; the highest non-NULL slot becomes Present_Value.
Relinquish_Default104yesThe value Present_Value takes when all 16 slots are NULL.
Feedback_Value40The state the equipment reports; a lasting mismatch is a command-failure alarm.

Priority array and relinquish

A write to Present_Value goes into one slot of the priority array: the priority in the WriteProperty request, or 16 when the request carries none. The multi-state output takes the value of the highest-priority slot that is not NULL. Writing NULL at a priority (relinquish) empties that slot; when all 16 are empty, Present_Value falls back to Relinquish_Default.

A value outside 1 to Number_Of_States is refused by the device (value-out-of-range).

PriorityUse in ASHRAE 135
1Manual-Life Safety
2Automatic-Life Safety
3Available
4Available
5Critical Equipment Control
6Minimum On/Off
7Available
8Manual Operator
9–16Available (16 is used when a write carries no priority)

COV

Every change of state or Status_Flags is reported.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

How do you write a BACnet multi-state output?

Write the state number (1 to Number_Of_States) to Present_Value at a priority. State_Text gives the name of each number; write NULL at the same priority to release the command.

Is a multi-state output always commandable?

Yes. Like analog and binary outputs, a multi-state output always has Priority_Array and Relinquish_Default.

Related object types

Download OTDeck, free for one connection BACnet client All object types

Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.