BACnet Analog Output object (AO, type 1)

The BACnet analog output object drives a physical analog output: a valve actuator, a damper, a variable-speed drive. It is always commandable: writes go into a 16-slot priority array, and the highest active priority wins.

Object type
1 (analog-output)
Common abbreviation
AO
Present_Value
REAL, in the units of Units
Commandable
Always: Priority_Array and Relinquish_Default are required
COV
Yes: on a change of at least COV_Increment, or of Status_Flags
In OTDeck
analog-output:1 or ao:1

What it is

An analog output stands for a physical analog output of the controller, usually 0–10 V or 4–20 mA scaled to percent or to an engineering value. Control programs, schedules, the BMS and operators all command it, each at its own priority.

Object type 1 in ASHRAE 135, written analog-output,N or AO-N.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Analog Output object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Present_Value85yesThe value in control: the highest-priority command, or Relinquish_Default when nothing commands it.
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Event_State36yesnormal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault).
Reliability103Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well.
Out_Of_Service81yesTRUE disconnects the physical output from Present_Value; the priority array keeps working, but the hardware is no longer driven by it.
Units117yesAn enumeration, not text: 62 is degrees-Celsius, 64 degrees-Fahrenheit, 98 percent, 29 percent-relative-humidity, 54 kilopascals, 95 no-units.
Priority_Array87yes16 slots, 1 highest. Each holds a commanded value or NULL; the highest non-NULL slot becomes Present_Value.
Relinquish_Default104yesThe value Present_Value takes when all 16 slots are NULL.
Min_Pres_Value69The lowest value the output accepts; a lower write is refused or clamped, depending on the device.
Max_Pres_Value65The highest value the output accepts.
COV_Increment22if COVThe smallest change of Present_Value that makes the device send a COV notification.

Worked example: A valve output through the priority array

analog-output:1, a heating valve in percent, Relinquish_Default 0.0. Three writers command it over a morning.

StepPriority array and Present_Value
06:00 the control program writes 35.0 at priority 16Slot 16: 35.0. Present_Value 35.0.
09:10 a technician writes 80.0 at priority 10 to test the valveSlots 10: 80.0 and 16: 35.0. Present_Value 80.0: the higher priority wins.
09:12 the program writes 40.0 at priority 16Slot 16 becomes 40.0, but Present_Value stays 80.0 while slot 10 holds a value.
09:20 the technician relinquishes priority 10Slot 10 is NULL again. Present_Value 40.0.
The program stops and relinquishes priority 16All slots NULL. Present_Value 0.0, the Relinquish_Default.

A forgotten write at priority 10 keeps the valve at 80 % for months. Relinquish every slot you wrote before you leave; OTDeck's write log and commissioning report list them.

Priority array and relinquish

A write to Present_Value goes into one slot of the priority array: the priority in the WriteProperty request, or 16 when the request carries none. The analog output takes the value of the highest-priority slot that is not NULL. Writing NULL at a priority (relinquish) empties that slot; when all 16 are empty, Present_Value falls back to Relinquish_Default.

Priority 8 (manual operator) is where many BMS front ends write an override; programs and schedules typically sit lower, at 10 to 16. A forgotten value at priority 8 holds the output until someone relinquishes it.

PriorityUse in ASHRAE 135
1Manual-Life Safety
2Automatic-Life Safety
3Available
4Available
5Critical Equipment Control
6Minimum On/Off
7Available
8Manual Operator
9–16Available (16 is used when a write carries no priority)

COV

COV on an analog output works as on an analog input: a notification when Present_Value moves by COV_Increment or Status_Flags change, so a subscriber also sees when another client takes over the output at a higher priority.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

What is the BACnet priority array?

Sixteen slots on a commandable object's Present_Value. Every command writes its value into one slot; the highest-priority slot that is not NULL becomes Present_Value. Priority 1 is the highest, 16 the lowest.

How do you release a BACnet override?

Write NULL to Present_Value at the same priority the override was written at. The slot empties and the next lower active slot, or Relinquish_Default, takes over.

What priority does a BACnet write use when none is given?

Priority 16, the lowest. On a commandable object any command at 1 to 15 still outranks it.