BACnet object reference · type 1
BACnet Analog Output object (AO, type 1)
The BACnet analog output object drives a physical analog output: a valve actuator, a damper, a variable-speed drive. It is always commandable: writes go into a 16-slot priority array, and the highest active priority wins.
- Object type
- 1 (analog-output)
- Common abbreviation
- AO
- Present_Value
- REAL, in the units of Units
- Commandable
- Always: Priority_Array and Relinquish_Default are required
- COV
- Yes: on a change of at least COV_Increment, or of Status_Flags
- In OTDeck
- analog-output:1 or ao:1
What it is
An analog output stands for a physical analog output of the controller, usually 0–10 V or 4–20 mA scaled to percent or to an engineering value. Control programs, schedules, the BMS and operators all command it, each at its own priority.
Object type 1 in ASHRAE 135, written analog-output,N or AO-N.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Analog Output object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Present_Value | 85 | yes | The value in control: the highest-priority command, or Relinquish_Default when nothing commands it. |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Event_State | 36 | yes | normal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault). |
| Reliability | 103 | Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well. | |
| Out_Of_Service | 81 | yes | TRUE disconnects the physical output from Present_Value; the priority array keeps working, but the hardware is no longer driven by it. |
| Units | 117 | yes | An enumeration, not text: 62 is degrees-Celsius, 64 degrees-Fahrenheit, 98 percent, 29 percent-relative-humidity, 54 kilopascals, 95 no-units. |
| Priority_Array | 87 | yes | 16 slots, 1 highest. Each holds a commanded value or NULL; the highest non-NULL slot becomes Present_Value. |
| Relinquish_Default | 104 | yes | The value Present_Value takes when all 16 slots are NULL. |
| Min_Pres_Value | 69 | The lowest value the output accepts; a lower write is refused or clamped, depending on the device. | |
| Max_Pres_Value | 65 | The highest value the output accepts. | |
| COV_Increment | 22 | if COV | The smallest change of Present_Value that makes the device send a COV notification. |
Worked example: A valve output through the priority array
analog-output:1, a heating valve in percent, Relinquish_Default 0.0. Three writers command it over a morning.
| Step | Priority array and Present_Value |
|---|---|
| 06:00 the control program writes 35.0 at priority 16 | Slot 16: 35.0. Present_Value 35.0. |
| 09:10 a technician writes 80.0 at priority 10 to test the valve | Slots 10: 80.0 and 16: 35.0. Present_Value 80.0: the higher priority wins. |
| 09:12 the program writes 40.0 at priority 16 | Slot 16 becomes 40.0, but Present_Value stays 80.0 while slot 10 holds a value. |
| 09:20 the technician relinquishes priority 10 | Slot 10 is NULL again. Present_Value 40.0. |
| The program stops and relinquishes priority 16 | All slots NULL. Present_Value 0.0, the Relinquish_Default. |
A forgotten write at priority 10 keeps the valve at 80 % for months. Relinquish every slot you wrote before you leave; OTDeck's write log and commissioning report list them.
Priority array and relinquish
A write to Present_Value goes into one slot of the priority array: the priority in the WriteProperty request, or 16 when the request carries none. The analog output takes the value of the highest-priority slot that is not NULL. Writing NULL at a priority (relinquish) empties that slot; when all 16 are empty, Present_Value falls back to Relinquish_Default.
Priority 8 (manual operator) is where many BMS front ends write an override; programs and schedules typically sit lower, at 10 to 16. A forgotten value at priority 8 holds the output until someone relinquishes it.
| Priority | Use in ASHRAE 135 |
|---|---|
| 1 | Manual-Life Safety |
| 2 | Automatic-Life Safety |
| 3 | Available |
| 4 | Available |
| 5 | Critical Equipment Control |
| 6 | Minimum On/Off |
| 7 | Available |
| 8 | Manual Operator |
| 9–16 | Available (16 is used when a write carries no priority) |
COV
COV on an analog output works as on an analog input: a notification when Present_Value moves by COV_Increment or Status_Flags change, so a subscriber also sees when another client takes over the output at a higher priority.
Typical uses in HVAC and BMS
- Heating and cooling valve positions in AHUs and fan coils, 0–100 %.
- Damper positions: outdoor air, return air, VAV boxes.
- Speed references for fans and pumps on variable-speed drives.
- Boiler and chiller setpoints exposed as outputs by plant controllers.
Field pitfalls
- A stuck override: a value at priority 8 left after a test outranks the control loop for good. Read the priority array, not only Present_Value.
- Writing without a priority writes at 16, the lowest: anything at 1–15 still wins, and the write seems to do nothing.
- Writing at priority 1 or 2 (life safety) takes the output away from every other command until it is relinquished.
- Relinquish_Default chosen carelessly: when every command is gone, a valve at Relinquish_Default 100 % opens fully.
- Min_Pres_Value and Max_Pres_Value: a write outside them is refused with value-out-of-range, often read as a communication fault.
Reading, writing and watching it in OTDeck
- Select analog-output:1 (or ao:1) in the object tree: OTDeck reads every property the device lists (Property_List, or the standard set on older devices) with ReadPropertyMultiple, and shows Present_Value large with its units and status flags.
- Watch it: the watch list subscribes with SubscribeCOV (lifetime 300 s, renewed while watched) and falls back to polling when the device refuses; the value goes to the trend panel next to MQTT, Modbus and OPC UA values.
- The panel shows the 16 slots of the priority array, the active one marked, Relinquish_Default, and a Relinquish action on each set slot.
- Write… writes Present_Value at the connection's write priority (16 by default) or one you pick, with the value shown as it will be sent; priorities 1–8 are refused unless the connection allows them. Writes are Pro, refused on read-only connections, need the connection name typed on production connections, and land in the write log as bacnet.write with the object, value and priority.
- The simulator's analog-output:1 Setpoint is commandable: write 95 at priority 16, see slot 16 set, then relinquish it.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
What is the BACnet priority array?
Sixteen slots on a commandable object's Present_Value. Every command writes its value into one slot; the highest-priority slot that is not NULL becomes Present_Value. Priority 1 is the highest, 16 the lowest.
How do you release a BACnet override?
Write NULL to Present_Value at the same priority the override was written at. The slot empties and the next lower active slot, or Relinquish_Default, takes over.
What priority does a BACnet write use when none is given?
Priority 16, the lowest. On a commandable object any command at 1 to 15 still outranks it.
Related object types
Download OTDeck, free for one connection BACnet client All object types
Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.