BACnet object reference · type 12
BACnet Loop object (type 12): PID control
The BACnet loop object exposes a PID control loop: it reads a controlled variable, compares it with a setpoint and writes its output to another object. Present_Value is the loop output.
- Object type
- 12 (loop)
- Common abbreviation
- LP
- Present_Value
- REAL: the loop output, in Output_Units
- Commandable
- No; it writes its output to the manipulated variable at Priority_For_Writing
- COV
- Yes: on a change of at least COV_Increment, or of Status_Flags
- In OTDeck
- loop:1
What it is
A loop ties three references together: the controlled variable (a temperature), the setpoint (a fixed value or another object), and the manipulated variable (usually an analog output) it writes its Present_Value to.
Object type 12 in ASHRAE 135. Many controllers run PID internally without exposing loop objects; when they do, the loop is the way to see and tune it over BACnet.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Loop object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Present_Value | 85 | yes | The output of the PID algorithm, in Output_Units. |
| Output_Units | 82 | Units of Present_Value, often percent. | |
| Manipulated_Variable_Reference | 60 | The object and property the loop writes (an analog output's Present_Value). | |
| Controlled_Variable_Reference | 19 | The object and property it controls (a sensor's Present_Value). | |
| Controlled_Variable_Value | 21 | The current value of the controlled variable. | |
| Setpoint_Reference | 109 | Where the setpoint comes from, when it is another object. | |
| Setpoint | 108 | The setpoint value in use. | |
| Action | 2 | direct or reverse: whether the output rises or falls when the controlled variable rises above setpoint. | |
| Proportional_Constant | 93 | P gain. | |
| Integral_Constant | 49 | I term. | |
| Derivative_Constant | 26 | D term. | |
| Bias | 14 | Output offset. | |
| Maximum_Output | 61 | Upper clamp of the output. | |
| Minimum_Output | 68 | Lower clamp of the output. | |
| Priority_For_Writing | 88 | The priority the loop writes its output at. | |
| COV_Increment | 22 | if COV | The smallest change of Present_Value that makes the device send a COV notification. |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Out_Of_Service | 81 | yes | TRUE stops the loop from writing; the output stays where it is. |
Commanding
A loop has no priority array. It is itself a commander: it writes the manipulated variable at Priority_For_Writing, so an operator override at a higher priority on that output takes the output away from the loop.
COV
Subscribing to a loop reports changes of Present_Value by COV_Increment and of Status_Flags, which is a cheap way to watch a loop's output while tuning.
Typical uses in HVAC and BMS
- Supply air temperature control through a heating or cooling valve.
- Duct static pressure control through a fan speed.
- Chilled water differential pressure control through pump speed.
Field pitfalls
- Action set the wrong way round: the valve opens further as the space overheats.
- An override on the manipulated output at a higher priority: the loop winds up while its output has no effect.
- Units of the integral and derivative constants differ between vendors (Integral_Constant_Units, Derivative_Constant_Units): check them before copying values between controllers.
Reading, writing and watching it in OTDeck
- Select loop:1 in the object tree: OTDeck reads every property the device lists (Property_List, or the standard set on older devices) with ReadPropertyMultiple, and shows Present_Value large with its units and status flags.
- Watch it: the watch list subscribes with SubscribeCOV (lifetime 300 s, renewed while watched) and falls back to polling when the device refuses; the value goes to the trend panel next to MQTT, Modbus and OPC UA values.
- Watch the loop's Present_Value next to its controlled variable and output on the trend panel to see how it behaves. OTDeck 0.7 writes Present_Value only, so tuning constants are read, not written.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
What is the Present_Value of a BACnet loop object?
The loop output: the value the PID algorithm writes to the object named in Manipulated_Variable_Reference, in Output_Units.
Is a BACnet loop commandable?
No. A loop has no priority array; it commands another object at its Priority_For_Writing.
Related object types