BACnet Loop object (type 12): PID control

The BACnet loop object exposes a PID control loop: it reads a controlled variable, compares it with a setpoint and writes its output to another object. Present_Value is the loop output.

Object type
12 (loop)
Common abbreviation
LP
Present_Value
REAL: the loop output, in Output_Units
Commandable
No; it writes its output to the manipulated variable at Priority_For_Writing
COV
Yes: on a change of at least COV_Increment, or of Status_Flags
In OTDeck
loop:1

What it is

A loop ties three references together: the controlled variable (a temperature), the setpoint (a fixed value or another object), and the manipulated variable (usually an analog output) it writes its Present_Value to.

Object type 12 in ASHRAE 135. Many controllers run PID internally without exposing loop objects; when they do, the loop is the way to see and tune it over BACnet.

Properties

Property identifiers as in ASHRAE 135. Required: present in every Loop object; blank: optional or required only in some configurations.

PropertyIdRequiredWhat it means in practice
Present_Value85yesThe output of the PID algorithm, in Output_Units.
Output_Units82Units of Present_Value, often percent.
Manipulated_Variable_Reference60The object and property the loop writes (an analog output's Present_Value).
Controlled_Variable_Reference19The object and property it controls (a sensor's Present_Value).
Controlled_Variable_Value21The current value of the controlled variable.
Setpoint_Reference109Where the setpoint comes from, when it is another object.
Setpoint108The setpoint value in use.
Action2direct or reverse: whether the output rises or falls when the controlled variable rises above setpoint.
Proportional_Constant93P gain.
Integral_Constant49I term.
Derivative_Constant26D term.
Bias14Output offset.
Maximum_Output61Upper clamp of the output.
Minimum_Output68Lower clamp of the output.
Priority_For_Writing88The priority the loop writes its output at.
COV_Increment22if COVThe smallest change of Present_Value that makes the device send a COV notification.
Status_Flags111yesFour bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point.
Out_Of_Service81yesTRUE stops the loop from writing; the output stays where it is.

Commanding

A loop has no priority array. It is itself a commander: it writes the manipulated variable at Priority_For_Writing, so an operator override at a higher priority on that output takes the output away from the loop.

COV

Subscribing to a loop reports changes of Present_Value by COV_Increment and of Status_Flags, which is a cheap way to watch a loop's output while tuning.

Typical uses in HVAC and BMS

Field pitfalls

Reading, writing and watching it in OTDeck

OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.

FAQ

What is the Present_Value of a BACnet loop object?

The loop output: the value the PID algorithm writes to the object named in Manipulated_Variable_Reference, in Output_Units.

Is a BACnet loop commandable?

No. A loop has no priority array; it commands another object at its Priority_For_Writing.