BACnet object reference · type 4
BACnet Binary Output object (BO, type 4): priority array and minimum on/off
The BACnet binary output object switches something on and off: a fan start, a pump, a relay. It is always commandable, so every command lands in its priority array, and minimum on and off times hold it at priority 6.
- Object type
- 4 (binary-output)
- Common abbreviation
- BO
- Present_Value
- BACnetBinaryPV: inactive (0) or active (1)
- Commandable
- Always: Priority_Array and Relinquish_Default are required
- COV
- Yes: on every change of Present_Value or Status_Flags
- In OTDeck
- binary-output:1 or bo:1
What it is
A binary output drives a relay or digital output of the controller: start/stop of a fan, enable of a chiller, open/close of a two-position valve.
Object type 4 in ASHRAE 135, written binary-output,N or BO-N.
Properties
Property identifiers as in ASHRAE 135. Required: present in every Binary Output object; blank: optional or required only in some configurations.
| Property | Id | Required | What it means in practice |
|---|---|---|---|
| Present_Value | 85 | yes | active or inactive: the winner of the priority array. |
| Status_Flags | 111 | yes | Four bits: in-alarm, fault, overridden, out-of-service. The quickest health check of a point. |
| Event_State | 36 | yes | normal, or the alarm state the object is in (high-limit, low-limit, offnormal, fault). |
| Reliability | 103 | Why a value is not trustworthy: no-sensor, over-range, under-range, open-loop, shorted-loop, communication-failure, and so on; no-fault-detected when all is well. | |
| Out_Of_Service | 81 | yes | TRUE disconnects the relay from Present_Value; commands still land in the priority array. |
| Polarity | 84 | yes | normal or reverse. Reverse inverts the relation between the physical contact and Present_Value. |
| Priority_Array | 87 | yes | 16 slots, 1 highest. Each holds a commanded value or NULL; the highest non-NULL slot becomes Present_Value. |
| Relinquish_Default | 104 | yes | The value Present_Value takes when all 16 slots are NULL. |
| Active_Text | 4 | What active means on site: Run, Open, Occupied, Alarm. | |
| Inactive_Text | 46 | What inactive means: Stop, Closed, Unoccupied, Normal. | |
| Minimum_On_Time | 67 | Seconds the output stays active after it turns on, held at priority 6. | |
| Minimum_Off_Time | 66 | Seconds it stays inactive after it turns off, held at priority 6. | |
| Feedback_Value | 40 | The state the equipment reports back; a mismatch with Present_Value for Time_Delay is a command-failure alarm. | |
| Elapsed_Active_Time | 33 | Seconds spent active since the last reset: run hours of a fan or pump. | |
| Change_Of_State_Count | 15 | How many times the value changed since the last reset: starts of a motor. |
Priority array and relinquish
A write to Present_Value goes into one slot of the priority array: the priority in the WriteProperty request, or 16 when the request carries none. The binary output takes the value of the highest-priority slot that is not NULL. Writing NULL at a priority (relinquish) empties that slot; when all 16 are empty, Present_Value falls back to Relinquish_Default.
Priority 6 is reserved for minimum on/off: when Present_Value changes and the object has Minimum_On_Time or Minimum_Off_Time, the device writes the new value at priority 6 itself and clears it when the time is over. Commands at 7 to 16 cannot switch the output back before then; commands at 1 to 5 can.
| Priority | Use in ASHRAE 135 |
|---|---|
| 1 | Manual-Life Safety |
| 2 | Automatic-Life Safety |
| 3 | Available |
| 4 | Available |
| 5 | Critical Equipment Control |
| 6 | Minimum On/Off |
| 7 | Available |
| 8 | Manual Operator |
| 9–16 | Available (16 is used when a write carries no priority) |
COV
Every change of Present_Value (or Status_Flags) is reported. Watching a binary output shows when another client takes it over at a higher priority.
Typical uses in HVAC and BMS
- Start/stop of supply and exhaust fans, pumps, cooling towers.
- Enable signals to chillers, boilers and packaged units.
- Two-position valves and dampers, lighting relays.
Field pitfalls
- A write that seems ignored: a minimum on or off time is holding the output at priority 6, or another command sits above yours. Read the priority array.
- Writing 1 as Unsigned or Boolean: the value must be Enumerated active/inactive; some devices accept other types, many do not.
- Hand-off-auto switches on the panel override the relay physically; Feedback_Value and a command-failure alarm are the only way the BMS sees it.
- A relinquish at the wrong priority does nothing: release the slot the override was written at.
Reading, writing and watching it in OTDeck
- Select binary-output:1 (or bo:1) in the object tree: OTDeck reads every property the device lists (Property_List, or the standard set on older devices) with ReadPropertyMultiple, and shows Present_Value large with its units and status flags.
- Watch it: the watch list subscribes with SubscribeCOV (lifetime 300 s, renewed while watched) and falls back to polling when the device refuses; the value goes to the trend panel next to MQTT, Modbus and OPC UA values.
- Write… takes active / inactive (or on/off, 1/0) and sends the Enumerated value; the priority array panel shows which slot holds the output, with Relinquish per slot. Priorities 1–8 are refused unless the connection allows them. Writes are Pro, refused on read-only connections, need the connection name typed on production connections, and land in the write log as bacnet.write with the object, value and priority.
- The simulator's binary-output:1 Pump command (Run / Stop) is commandable.
OTDeck is a BACnet/IP and BACnet/SC client for macOS, Windows and Linux; discovering, reading and watching are free for one connection.
FAQ
Why does a BACnet binary output not change when I write it?
Usually another command holds it at a higher priority, or a minimum on or off time holds it at priority 6. Read the priority array to see which slot is active.
What is priority 6 in BACnet?
Minimum On/Off. A binary output with Minimum_On_Time or Minimum_Off_Time writes its new state at priority 6 for that time, so lower-priority commands cannot short-cycle the equipment.
How do you write a BACnet binary output?
Write active or inactive (Enumerated 1 or 0) to Present_Value at a priority; write NULL at the same priority to release it.
Related object types
Download OTDeck, free for one connection BACnet client All object types
Object type numbers and property identifiers follow ASHRAE 135 (BACnet). Devices differ in which optional properties they implement; read the object's Property_List for the real set. Found a mistake? Write to support@otdeck.com. BACnet is a trademark of ASHRAE; OTDeck is not affiliated with ASHRAE.