Video · 2:34
BACnet explorer for Mac, Windows and Linux: BACnet/IP and BACnet/SC in OTDeck
Who-Is discovery, objects and properties, the priority array with writes and relinquish, a COV watch list, trend logs, alarm acknowledgement, and a BACnet/SC hub connection with an operational certificate, on the built-in simulator.
Recorded on OTDeck 0.6.0 with the built-in simulator, no cuts. Narrated; captions in the player. Also on YouTube.
What the video shows
- Adding the simulator's BACnet/IP boiler and finding it with Who-Is.
- Objects grouped by type with their names; every property of the supply temperature, with units and status flags.
- A COV subscription from the watch list, plotted in the trend panel.
- Writing a setpoint at a priority, the 16-slot priority array, and relinquishing it again.
- A trend log read with ReadRange, and an alarm acknowledged with AcknowledgeAlarm.
- Connecting to a BACnet/SC hub with an operational certificate and reading a second device behind it.
Transcript
0:01 OTDeck 0.6 adds BACnet: BACnet IP and BACnet SC, next to MQTT, Modbus and OPC UA, on Mac, Windows and Linux.
0:12 The built-in simulator has a BACnet boiler; we add it and connect.
0:21 Boiler 7 answers the Who-Is.
0:23 Its objects come grouped by type, with their names.
0:27 Supply temperature: the present value in degrees, status flags, every property.
0:32 The eye puts it on the watch list with a COV subscription, and the trend panel plots it.
0:44 The setpoint is commandable: sixteen priority slots.
0:48 We write 95 at priority 16; the slot shows it, and any slot can be relinquished.
0:54 Priorities one to eight stay refused unless you allow them on the connection.
1:07 The trend log object keeps a history on the device itself: read range by last N, by position or by time, as a table and a chart, with CSV export.
1:20 The supply temperature crossed its high limit.
1:23 The alarm shows the transition and its time stamp, and we acknowledge it with the device's own stamp.
1:30 Every write and every acknowledgement lands in the write log.
1:39 BACnet SC is the secure transport: a TLS hub.
1:42 The simulator runs one with a test CA.
1:45 The connection takes your operational certificate, key and CA, checks them, and can make a CSR for your CA to sign.
1:54 Connect, and the same boiler appears through the hub, addressed by its VMAC.
2:09 Reading is free forever for one connection.
2:13 Writes, acknowledgements and BACnet SC come with OTDeck Pro, 99 dollars once.
2:19 AI agents browse and read BACnet through the built-in MCP server, and ask you before every write.
2:28 otdeck dot com.