Solar inverter · Modbus TCP / RTU

SunSpec Inverter (three-phase, model 103) Modbus register map

Generic SunSpec map: Common model 1 followed directly by the integer three-phase inverter model 103, base address 40000. 50 registers below, copied from the vendor's document; OTDeck adds them to a connection with Register map → Add from library.

Also covers
SunSpec model 1 + 103, SunSpec Inverter (Three Phase)
Link
Modbus TCP, Modbus RTU (RS-485)
Source
SunSpec Information Models, model_1.json (Common) and model_103.json (Inverter (Three Phase)), github.com/sunspec/models, master (latest release tag v2026-04-20) (2025-07-05 (last change to model_103.json))
Addresses
SunSpec model definitions give point offsets inside each model (ID at offset 0, L at 1). Address here = 0-based protocol address = base (40000) + model start offset + point offset. Model 1 start = 40002 (model 1 JSON: https://raw.githubusercontent.com/sunspec/models/master/json/model_1.json), model 103 start = 40002 + 68 = 40070. Some vendor docs print these as 1-based registers 40001.., which are one higher.

SunSpec devices place the 'SunS' marker at a base address that can be 0, 40000 or 50000 (40000 assumed here); model 1 starts at base+2. This template ALSO ASSUMES model 1 has length 66 (68 registers including ID and L) and that model 103 follows it directly at base+70. That is only true for devices with exactly that layout. A correct client walks the model chain: read ID and L at each model start, next model starts at start + 2 + L, chain ends with ID 0xFFFF. If 'Model 103 ID' does not read 103, this layout does not apply (the device may use model 101/102, the float models 111-113, or put other models first). All registers are holding registers (function 03). Values use dynamic scale factors (sunssf, int16 exponent) in separate registers; read the value and its scale factor in the same request. Not-implemented values (per SunSpec Alliance pysunspec2 sunspec2/mb.py): 0xFFFF for uint16/enum16/bitfield16, 0x8000 (-32768) for int16 and sunssf, 0 for acc32, 0xFFFFFFFF for bitfield32, NUL for strings. The end of the model chain is ID 0xFFFF. pysunspec2 scans base addresses 40000, 0, 50000 in that order. Strings are 2 ASCII chars per register. Multi-register values are high word first.

Registers

Address: the 0-based protocol address sent on the wire. Ref: the same register in 1-based notation (40001 = holding 0). Scale: multiply the raw value by it.

NameTableAddressRefTypeOrderScaleUnit
SunSpec marker 'SunS'Must read 'SunS' (0x53756E53). If not, try base 0 or 50000.Holding40000–40001440001string[2]
Model 1 IDCommon model; must be 1.Holding40002440003uint16
Model 1 length66 for the standard common model.Holding40003440004uint16
ManufacturerMn: well-known value registered with SunSpec.Holding40004–40019440005string[16]
ModelMd: manufacturer specific value (32 chars).Holding40020–40035440021string[16]
OptionsOpt (16 chars).Holding40036–40043440037string[8]
VersionVr (16 chars).Holding40044–40051440045string[8]
Serial numberSN (32 chars).Holding40052–40067440053string[16]
Device addressWritable. DA: Modbus device address.Holding40068440069uint16
Model 103 IDMust be 103 for this layout (101 = single phase, 102 = split phase, 111-113 = float variants).Holding40070440071uint16
Model 103 length50 for model 103.Holding40071440072uint16
AC current (total)Multiply by 10^(Current scale factor at address 40076).Holding40072440073uint16A
Phase A currentMultiply by 10^(Current scale factor at address 40076).Holding40073440074uint16A
Phase B currentMultiply by 10^(Current scale factor at address 40076).Holding40074440075uint16A
Phase C currentMultiply by 10^(Current scale factor at address 40076).Holding40075440076uint16A
Current scale factorA_SF (sunssf).Holding40076440077int16
Voltage ABMultiply by 10^(Voltage scale factor at address 40083).Holding40077440078uint16V
Voltage BCMultiply by 10^(Voltage scale factor at address 40083).Holding40078440079uint16V
Voltage CAMultiply by 10^(Voltage scale factor at address 40083).Holding40079440080uint16V
Voltage ANMultiply by 10^(Voltage scale factor at address 40083).Holding40080440081uint16V
Voltage BNMultiply by 10^(Voltage scale factor at address 40083).Holding40081440082uint16V
Voltage CNMultiply by 10^(Voltage scale factor at address 40083).Holding40082440083uint16V
Voltage scale factorV_SF (sunssf).Holding40083440084int16
AC powerMultiply by 10^(AC power scale factor at address 40085).Holding40084440085int16W
AC power scale factorW_SF (sunssf).Holding40085440086int16
Line frequencyMultiply by 10^(Frequency scale factor at address 40087).Holding40086440087uint16Hz
Frequency scale factorHz_SF (sunssf).Holding40087440088int16
AC apparent powerMultiply by 10^(Apparent power scale factor at address 40089).Holding40088440089int16VA
Apparent power scale factorVA_SF (sunssf).Holding40089440090int16
AC reactive powerMultiply by 10^(Reactive power scale factor at address 40091).Holding40090440091int16var
Reactive power scale factorVAr_SF (sunssf).Holding40091440092int16
AC power factorMultiply by 10^(Power factor scale factor at address 40093). Units per model definition: Pct.Holding40092440093int16%
Power factor scale factorPF_SF (sunssf).Holding40093440094int16
AC energy (lifetime)Multiply by 10^(Energy scale factor at address 40096). acc32 accumulator.Holding40094–40095440095uint32ABCDWh
Energy scale factorWH_SF (sunssf).Holding40096440097int16
DC currentMultiply by 10^(DC current scale factor at address 40098).Holding40097440098uint16A
DC current scale factorDCA_SF (sunssf).Holding40098440099int16
DC voltageMultiply by 10^(DC voltage scale factor at address 40100).Holding40099440100uint16V
DC voltage scale factorDCV_SF (sunssf).Holding40100440101int16
DC powerMultiply by 10^(DC power scale factor at address 40102).Holding40101440102int16W
DC power scale factorDCW_SF (sunssf).Holding40102440103int16
Cabinet temperatureMultiply by 10^(Temperature scale factor at address 40107).Holding40103440104int16°C
Heat sink temperatureMultiply by 10^(Temperature scale factor at address 40107).Holding40104440105int16°C
Transformer temperatureMultiply by 10^(Temperature scale factor at address 40107).Holding40105440106int16°C
Other temperatureMultiply by 10^(Temperature scale factor at address 40107).Holding40106440107int16°C
Temperature scale factorTmp_SF (sunssf).Holding40107440108int16
Operating stateenum16 St: 1 OFF, 2 SLEEPING, 3 STARTING, 4 MPPT, 5 THROTTLED, 6 SHUTTING_DOWN, 7 FAULT, 8 STANDBY.Holding40108440109uint16
Vendor operating stateenum16 StVnd: vendor specific operating state code.Holding40109440110uint16
Event bitfield 1bitfield32 Evt1: event fields (bit definitions in the SunSpec model 103 definition).Holding40110–40111440111uint32ABCD
Vendor event bitfield 1bitfield32 EvtVnd1: vendor defined events.Holding40114–40115440115uint32ABCD

Check the firmware and document version of your device against the source; registers differ between versions. Found a mistake? Write to support@otdeck.com. Product names are trademarks of their owners; OTDeck is not affiliated with them.