OTDeck

Energy meter · Modbus RTU

Schneider Electric iEM3255 Modbus register map

Acti9 iEM3100/3200/3300 series three-phase DIN-rail energy meter; the x150/x155/x250/x255/x350/x355 models have RS-485 Modbus RTU. 47 registers below, copied from the vendor's document; OTDeck adds them to a connection with Register map → Add from library.

Also covers
iEM3150, iEM3155, iEM3250, iEM3350, iEM3355, A9MEM3150, A9MEM3155, A9MEM3250, A9MEM3255, A9MEM3350, A9MEM3355
Link
Modbus RTU (RS-485)
Serial default
8?1
Source
Energy meters iEM3100 / iEM3200 / iEM3300 series User manual, DOCA0005EN-16 (05/2026)
Addresses
The manual's register tables give 'Address' (16-bit hex, the value used in the Modbus frame) and 'Register' (decimal, register = address + 1). Address here = the hex Address column (e.g. Register 3000 -> 0x0BB7 = 2999).

Supported functions: 03 Read Holding Registers, 16 Write Multiple Registers (used for the command interface at 0x1481), 43/14 Read Device Identification. Configuration registers marked R/WC are changed through the command interface (function 16), not by writing the register directly. Settings (set on the display): baud 9600/19200/38400, parity Even/Odd/None, stop bits always 1, address 1-247; the manual does not state factory defaults for these. Several registers are not applicable to the iEM3150/iEM3250/iEM3350 (noted per register). Energies are also available as Int64 in Wh/VARh at 0x0C83 etc.; this template uses the Float32 kWh copies at 0xB02B. The manual does not state the word order for Float32/UInt32 explicitly; the template assumes the Modbus-usual high word first. The iEM3100/iEM3200/iEM3300 non-Modbus models (M-Bus, LON, BACnet) are not covered.

Registers

Address: the 0-based protocol address sent on the wire. Ref: the same register in 1-based notation (40001 = holding 0). Scale: multiply the raw value by it.

NameTableAddressRefTypeOrderScaleUnit
Meter nameUTF8, 20 registers.Holding29–4840030string[20]
Meter modelUTF8, 20 registers.Holding49–6840050string[20]
ManufacturerUTF8, 20 registers.Holding69–8840070string[20]
Serial numberHolding129–13040130uint32ABCD
Present firmware versionDLF format: X.Y.ZTT.Holding163641637uint16
Number of phasesHolding201342014uint16
Number of wiresHolding201442015uint16
Power system0 = 1PH2W L-N, 1 = 1PH2W L-L, 2 = 1PH3W L-L with N, 3 = 3PH3W, 11 = 3PH4W, 13 = 1PH4W multi L with N. Written via the command interface (R/WC).Holding201542016uint16
Nominal frequencyHolding201642017uint16Hz
Modbus addressR/WC: changed via the command interface, not by direct write.Holding650046501uint16
Baud rate0 = 9600, 1 = 19200, 2 = 38400. R/WC.Holding650146502uint16
Parity0 = Even, 1 = Odd, 2 = None. Stop bits = 1. R/WC.Holding650246503uint16
I1 phase 1 currentHolding2999–300043000float32ABCDA
I2 phase 2 currentHolding3001–300243002float32ABCDA
I3 phase 3 currentHolding3003–300443004float32ABCDA
Current averageHolding3009–301043010float32ABCDA
Voltage L1-L2Holding3019–302043020float32ABCDV
Voltage L2-L3Holding3021–302243022float32ABCDV
Voltage L3-L1Holding3023–302443024float32ABCDV
Voltage L-L averageHolding3025–302643026float32ABCDV
Voltage L1-NHolding3027–302843028float32ABCDV
Voltage L2-NHolding3029–303043030float32ABCDV
Voltage L3-NHolding3031–303243032float32ABCDV
Voltage L-N averageHolding3035–303643036float32ABCDV
Active power phase 1Holding3053–305443054float32ABCDkW
Active power phase 2Holding3055–305643056float32ABCDkW
Active power phase 3Holding3057–305843058float32ABCDkW
Total active powerHolding3059–306043060float32ABCDkW
Total reactive powerNot applicable for iEM3150 / iEM3250 / iEM3350.Holding3067–306843068float32ABCDkvar
Total apparent powerNot applicable for iEM3150 / iEM3250 / iEM3350.Holding3075–307643076float32ABCDkVA
Total power factor-1<PF<0 = Q2 (P negative, capacitive); -2<PF<-1 = Q3 (P negative, inductive); 0<PF<1 = Q1 (P positive, inductive); 1<PF<2 = Q4 (P positive, capacitive).Holding3083–308443084float32ABCD
FrequencyHolding3109–311043110float32ABCDHz
Multi-tariff active rate0 = multi tariff disabled, 1 to 4 = rate A to D. R/WC. Not applicable for iEM3150 / iEM3250 / iEM3350.Holding419044191uint16
Diagnostics error statusBitmap: bit0 = code 101, bit1 = 102, bit2 = 201, bit3 = 202, bit4 = 203, bit5 = 204, bit6 = 205, bit7 = 206, bit8 = 207 (1 = active).Holding44999445000uint16
Total active energy importCannot be reset.Holding45099–45100445100float32ABCDkWh
Total active energy exportCannot be reset. Not applicable for iEM3150 / iEM3250 / iEM3350.Holding45101–45102445102float32ABCDkWh
Total reactive energy importNot applicable for iEM3150 / iEM3250 / iEM3350.Holding45103–45104445104float32ABCDkvarh
Total reactive energy exportNot applicable for iEM3150 / iEM3250 / iEM3350.Holding45105–45106445106float32ABCDkvarh
Partial active energy importHolding45107–45108445108float32ABCDkWh
Partial reactive energy importNot applicable for iEM3150 / iEM3250 / iEM3350.Holding45109–45110445110float32ABCDkvarh
Active energy import phase 1Holding45111–45112445112float32ABCDkWh
Active energy import phase 2Holding45113–45114445114float32ABCDkWh
Active energy import phase 3Holding45115–45116445116float32ABCDkWh
Rate A active energy importiEM3155 / iEM3255 / iEM3355 only.Holding45119–45120445120float32ABCDkWh
Rate B active energy importiEM3155 / iEM3255 / iEM3355 only.Holding45121–45122445122float32ABCDkWh
Rate C active energy importiEM3155 / iEM3255 / iEM3355 only.Holding45123–45124445124float32ABCDkWh
Rate D active energy importiEM3155 / iEM3255 / iEM3355 only.Holding45125–45126445126float32ABCDkWh

Check the firmware and document version of your device against the source; registers differ between versions. Found a mistake? Write to support@otdeck.com. Product names are trademarks of their owners; OTDeck is not affiliated with them.