Eastron SDM630 Modbus register map

Three-phase DIN-rail multifunction energy meter with RS-485 Modbus RTU. 58 registers below, copied from the vendor's document; OTDeck adds them to a connection with Register map → Add from library.

Also covers
SDM630Modbus, SDM630-Modbus V2
Link
Modbus RTU (RS-485)
Serial default
9600 baud, 8N1
Unit id default
1
Source
Eastron SDM630Modbus Smart Meter Modbus Protocol Implementation, V1.8
Addresses
The doc lists 3X/4X register references (30001 / 40001 based) together with the 'Modbus Protocol Start Address Hex'. Address here = reference - 30001 (input) or reference - 40001 (holding), which equals the hex start address printed in the doc (e.g. 30001 -> 0x0000, 30343 -> 0x0156). Source PDF is Eastron's own protocol document, re-hosted by distributor Fastron Electronics in its 'Eastron Europe' folder (Eastron Europe's own downloads require a login).

Function code 04 reads input (3X) registers, 03 reads and 16 writes holding (4X) registers; write only one parameter per message. All values are 32-bit IEEE 754 floats in two registers, most significant register first by default (changeable via the holding 'Register Order' parameter by writing 2141.0). Requests must use an even start address and an even register count. Maximum 40 values (80 registers) per request. Parameters valid only for some wiring systems return 0 otherwise (e.g. phase 2/3 values in 1p2w). Address 1-247, broadcast (0) supported. Defaults per doc: 9600 baud, one stop bit, no parity, node 1; 8 data bits per RTU framing. Some holding registers need the password (default 0000) written to 40025 first. Note: the SDM630MCT, SDM630MCT-2T and SDM630-Modbus V3 have their own protocol documents; verify the register list before using this template on them.

Registers

Address: the 0-based protocol address sent on the wire. Ref: the same register in 1-based notation (40001 = holding 0). Scale: multiply the raw value by it.

NameTableAddressRefTypeOrderScaleUnit
Phase 1 line to neutral voltageInput0–130001float32ABCDV
Phase 2 line to neutral voltageInput2–330003float32ABCDV
Phase 3 line to neutral voltageInput4–530005float32ABCDV
Phase 1 currentInput6–730007float32ABCDA
Phase 2 currentInput8–930009float32ABCDA
Phase 3 currentInput10–1130011float32ABCDA
Phase 1 powerInput12–1330013float32ABCDW
Phase 2 powerInput14–1530015float32ABCDW
Phase 3 powerInput16–1730017float32ABCDW
Phase 1 apparent powerInput18–1930019float32ABCDVA
Phase 2 apparent powerInput20–2130021float32ABCDVA
Phase 3 apparent powerInput22–2330023float32ABCDVA
Phase 1 reactive powerInput24–2530025float32ABCDvar
Phase 2 reactive powerInput26–2730027float32ABCDvar
Phase 3 reactive powerInput28–2930029float32ABCDvar
Phase 1 power factorSign indicates current direction: positive = forward, negative = reverse.Input30–3130031float32ABCD
Phase 2 power factorSign indicates current direction: positive = forward, negative = reverse.Input32–3330033float32ABCD
Phase 3 power factorSign indicates current direction: positive = forward, negative = reverse.Input34–3530035float32ABCD
Average line to neutral voltageInput42–4330043float32ABCDV
Average line currentInput46–4730047float32ABCDA
Sum of line currentsInput48–4930049float32ABCDA
Total system powerInput52–5330053float32ABCDW
Total system apparent powerInput56–5730057float32ABCDVA
Total system reactive powerInput60–6130061float32ABCDvar
Total system power factorSign indicates current direction: positive = forward, negative = reverse.Input62–6330063float32ABCD
FrequencyFrequency of supply voltages.Input70–7130071float32ABCDHz
Total import active energyInput72–7330073float32ABCDkWh
Total export active energyInput74–7530075float32ABCDkWh
Total import reactive energyInput76–7730077float32ABCDkvarh
Total export reactive energyInput78–7930079float32ABCDkvarh
Total apparent energyInput80–8130081float32ABCDkVAh
AhInput82–8330083float32ABCDAh
Total system power demandPower sum demand is import - export.Input84–8530085float32ABCDW
Line 1 to line 2 voltageInput200–20130201float32ABCDV
Line 2 to line 3 voltageInput202–20330203float32ABCDV
Line 3 to line 1 voltageInput204–20530205float32ABCDV
Average line to line voltageInput206–20730207float32ABCDV
Neutral currentInput224–22530225float32ABCDA
Phase 1 L/N voltage THDInput234–23530235float32ABCD%
Phase 2 L/N voltage THDInput236–23730237float32ABCD%
Phase 3 L/N voltage THDInput238–23930239float32ABCD%
Phase 1 current THDInput240–24130241float32ABCD%
Phase 2 current THDInput242–24330243float32ABCD%
Phase 3 current THDInput244–24530245float32ABCD%
Total active energyImport + export.Input342–34330343float32ABCDkWh
Total reactive energyImport + export.Input344–34530345float32ABCDkvarh
L1 import active energyInput346–34730347float32ABCDkWh
L2 import active energyInput348–34930349float32ABCDkWh
L3 import active energyInput350–35130351float32ABCDkWh
L1 export active energyInput352–35330353float32ABCDkWh
L2 export active energyInput354–35530355float32ABCDkWh
L3 export active energyInput356–35730357float32ABCDkWh
Demand periodWritable. Demand period in minutes: 0, 5, 8, 10, 15, 20, 30 or 60; default 60.Holding2–340003float32ABCDmin
System typeWritable (password protected). 3 = 3p4w, 2 = 3p3w, 1 = 1p2w.Holding10–1140011float32ABCD
Network parity/stopWritable. 0 = 1 stop bit no parity (default), 1 = 1 stop even, 2 = 1 stop odd, 3 = 2 stop no parity. Restart required.Holding18–1940019float32ABCD
Network node (Modbus address)Writable. 1 to 247, default 1. Restart required.Holding20–2140021float32ABCD
Network baud rateWritable. 0 = 2400, 1 = 4800, 2 = 9600 (default), 3 = 19200, 4 = 38400.Holding28–2940029float32ABCD
Serial numberRead only. Register 464513 (0xFC00), unsigned int32.Holding64512–64513464513uint32ABCD

Check the firmware and document version of your device against the source; registers differ between versions. Found a mistake? Write to support@otdeck.com. Product names are trademarks of their owners; OTDeck is not affiliated with them.