Energy meter · Modbus RTU
Eastron SDM630 Modbus register map
Three-phase DIN-rail multifunction energy meter with RS-485 Modbus RTU. 58 registers below, copied from the vendor's document; OTDeck adds them to a connection with Register map → Add from library.
- Also covers
- SDM630Modbus, SDM630-Modbus V2
- Link
- Modbus RTU (RS-485)
- Serial default
- 9600 baud, 8N1
- Unit id default
- 1
- Source
- Eastron SDM630Modbus Smart Meter Modbus Protocol Implementation, V1.8
- Addresses
- The doc lists 3X/4X register references (30001 / 40001 based) together with the 'Modbus Protocol Start Address Hex'. Address here = reference - 30001 (input) or reference - 40001 (holding), which equals the hex start address printed in the doc (e.g. 30001 -> 0x0000, 30343 -> 0x0156). Source PDF is Eastron's own protocol document, re-hosted by distributor Fastron Electronics in its 'Eastron Europe' folder (Eastron Europe's own downloads require a login).
Function code 04 reads input (3X) registers, 03 reads and 16 writes holding (4X) registers; write only one parameter per message. All values are 32-bit IEEE 754 floats in two registers, most significant register first by default (changeable via the holding 'Register Order' parameter by writing 2141.0). Requests must use an even start address and an even register count. Maximum 40 values (80 registers) per request. Parameters valid only for some wiring systems return 0 otherwise (e.g. phase 2/3 values in 1p2w). Address 1-247, broadcast (0) supported. Defaults per doc: 9600 baud, one stop bit, no parity, node 1; 8 data bits per RTU framing. Some holding registers need the password (default 0000) written to 40025 first. Note: the SDM630MCT, SDM630MCT-2T and SDM630-Modbus V3 have their own protocol documents; verify the register list before using this template on them.
Registers
Address: the 0-based protocol address sent on the wire. Ref: the same register in 1-based notation (40001 = holding 0). Scale: multiply the raw value by it.
| Name | Table | Address | Ref | Type | Order | Scale | Unit |
|---|---|---|---|---|---|---|---|
| Phase 1 line to neutral voltage | Input | 0–1 | 30001 | float32 | ABCD | V | |
| Phase 2 line to neutral voltage | Input | 2–3 | 30003 | float32 | ABCD | V | |
| Phase 3 line to neutral voltage | Input | 4–5 | 30005 | float32 | ABCD | V | |
| Phase 1 current | Input | 6–7 | 30007 | float32 | ABCD | A | |
| Phase 2 current | Input | 8–9 | 30009 | float32 | ABCD | A | |
| Phase 3 current | Input | 10–11 | 30011 | float32 | ABCD | A | |
| Phase 1 power | Input | 12–13 | 30013 | float32 | ABCD | W | |
| Phase 2 power | Input | 14–15 | 30015 | float32 | ABCD | W | |
| Phase 3 power | Input | 16–17 | 30017 | float32 | ABCD | W | |
| Phase 1 apparent power | Input | 18–19 | 30019 | float32 | ABCD | VA | |
| Phase 2 apparent power | Input | 20–21 | 30021 | float32 | ABCD | VA | |
| Phase 3 apparent power | Input | 22–23 | 30023 | float32 | ABCD | VA | |
| Phase 1 reactive power | Input | 24–25 | 30025 | float32 | ABCD | var | |
| Phase 2 reactive power | Input | 26–27 | 30027 | float32 | ABCD | var | |
| Phase 3 reactive power | Input | 28–29 | 30029 | float32 | ABCD | var | |
| Phase 1 power factorSign indicates current direction: positive = forward, negative = reverse. | Input | 30–31 | 30031 | float32 | ABCD | ||
| Phase 2 power factorSign indicates current direction: positive = forward, negative = reverse. | Input | 32–33 | 30033 | float32 | ABCD | ||
| Phase 3 power factorSign indicates current direction: positive = forward, negative = reverse. | Input | 34–35 | 30035 | float32 | ABCD | ||
| Average line to neutral voltage | Input | 42–43 | 30043 | float32 | ABCD | V | |
| Average line current | Input | 46–47 | 30047 | float32 | ABCD | A | |
| Sum of line currents | Input | 48–49 | 30049 | float32 | ABCD | A | |
| Total system power | Input | 52–53 | 30053 | float32 | ABCD | W | |
| Total system apparent power | Input | 56–57 | 30057 | float32 | ABCD | VA | |
| Total system reactive power | Input | 60–61 | 30061 | float32 | ABCD | var | |
| Total system power factorSign indicates current direction: positive = forward, negative = reverse. | Input | 62–63 | 30063 | float32 | ABCD | ||
| FrequencyFrequency of supply voltages. | Input | 70–71 | 30071 | float32 | ABCD | Hz | |
| Total import active energy | Input | 72–73 | 30073 | float32 | ABCD | kWh | |
| Total export active energy | Input | 74–75 | 30075 | float32 | ABCD | kWh | |
| Total import reactive energy | Input | 76–77 | 30077 | float32 | ABCD | kvarh | |
| Total export reactive energy | Input | 78–79 | 30079 | float32 | ABCD | kvarh | |
| Total apparent energy | Input | 80–81 | 30081 | float32 | ABCD | kVAh | |
| Ah | Input | 82–83 | 30083 | float32 | ABCD | Ah | |
| Total system power demandPower sum demand is import - export. | Input | 84–85 | 30085 | float32 | ABCD | W | |
| Line 1 to line 2 voltage | Input | 200–201 | 30201 | float32 | ABCD | V | |
| Line 2 to line 3 voltage | Input | 202–203 | 30203 | float32 | ABCD | V | |
| Line 3 to line 1 voltage | Input | 204–205 | 30205 | float32 | ABCD | V | |
| Average line to line voltage | Input | 206–207 | 30207 | float32 | ABCD | V | |
| Neutral current | Input | 224–225 | 30225 | float32 | ABCD | A | |
| Phase 1 L/N voltage THD | Input | 234–235 | 30235 | float32 | ABCD | % | |
| Phase 2 L/N voltage THD | Input | 236–237 | 30237 | float32 | ABCD | % | |
| Phase 3 L/N voltage THD | Input | 238–239 | 30239 | float32 | ABCD | % | |
| Phase 1 current THD | Input | 240–241 | 30241 | float32 | ABCD | % | |
| Phase 2 current THD | Input | 242–243 | 30243 | float32 | ABCD | % | |
| Phase 3 current THD | Input | 244–245 | 30245 | float32 | ABCD | % | |
| Total active energyImport + export. | Input | 342–343 | 30343 | float32 | ABCD | kWh | |
| Total reactive energyImport + export. | Input | 344–345 | 30345 | float32 | ABCD | kvarh | |
| L1 import active energy | Input | 346–347 | 30347 | float32 | ABCD | kWh | |
| L2 import active energy | Input | 348–349 | 30349 | float32 | ABCD | kWh | |
| L3 import active energy | Input | 350–351 | 30351 | float32 | ABCD | kWh | |
| L1 export active energy | Input | 352–353 | 30353 | float32 | ABCD | kWh | |
| L2 export active energy | Input | 354–355 | 30355 | float32 | ABCD | kWh | |
| L3 export active energy | Input | 356–357 | 30357 | float32 | ABCD | kWh | |
| Demand periodWritable. Demand period in minutes: 0, 5, 8, 10, 15, 20, 30 or 60; default 60. | Holding | 2–3 | 40003 | float32 | ABCD | min | |
| System typeWritable (password protected). 3 = 3p4w, 2 = 3p3w, 1 = 1p2w. | Holding | 10–11 | 40011 | float32 | ABCD | ||
| Network parity/stopWritable. 0 = 1 stop bit no parity (default), 1 = 1 stop even, 2 = 1 stop odd, 3 = 2 stop no parity. Restart required. | Holding | 18–19 | 40019 | float32 | ABCD | ||
| Network node (Modbus address)Writable. 1 to 247, default 1. Restart required. | Holding | 20–21 | 40021 | float32 | ABCD | ||
| Network baud rateWritable. 0 = 2400, 1 = 4800, 2 = 9600 (default), 3 = 19200, 4 = 38400. | Holding | 28–29 | 40029 | float32 | ABCD | ||
| Serial numberRead only. Register 464513 (0xFC00), unsigned int32. | Holding | 64512–64513 | 464513 | uint32 | ABCD |
Check the firmware and document version of your device against the source; registers differ between versions. Found a mistake? Write to support@otdeck.com. Product names are trademarks of their owners; OTDeck is not affiliated with them.