Eastron SDM230 Modbus register map

Single-phase two-tariff DIN-rail energy meter with RS-485 Modbus RTU. 29 registers below, copied from the vendor's document; OTDeck adds them to a connection with Register map → Add from library.

Also covers
SDM230-Modbus, SDM230-2T
Link
Modbus RTU (RS-485)
Serial default
9600 baud, 8N1
Unit id default
1
Source
Eastron SDM230Modbus Protocol, V1.1
Addresses
The doc lists 3X/4X register references (30001 / 40001 based) together with the 'Modbus Protocol Start Address Hex'. Address here = reference - 30001 (input) or reference - 40001 (holding), which equals the hex start address printed in the doc (e.g. 30001 -> 0x0000, 30343 -> 0x0156). Source PDF is Jiaxing Eastron's own document, re-hosted by distributor Fastron Electronics in its 'Eastron Europe' folder.

Function code 04 reads input (3X), 03 reads and 16 writes holding (4X) registers. All values are 32-bit IEEE 754 floats in two registers, most significant register first by default (changeable via 'Register Order'). Start address and register count must be even. Maximum 30 values (60 registers) per request. Address 1-247, broadcast supported. Defaults per doc: 9600 baud, one stop bit, no parity, node 1; 8 data bits per RTU framing.

Registers

Address: the 0-based protocol address sent on the wire. Ref: the same register in 1-based notation (40001 = holding 0). Scale: multiply the raw value by it.

NameTableAddressRefTypeOrderScaleUnit
VoltagePhase 1 line to neutral volts.Input0–130001float32ABCDV
CurrentInput6–730007float32ABCDA
Active powerInput12–1330013float32ABCDW
Apparent powerInput18–1930019float32ABCDVA
Reactive powerInput24–2530025float32ABCDvar
Power factorInput30–3130031float32ABCD
Phase angleInput36–3730037float32ABCD°
FrequencyInput70–7130071float32ABCDHz
Import active energySince last reset.Input72–7330073float32ABCDkWh
Export active energySince last reset.Input74–7530075float32ABCDkWh
Import reactive energySince last reset.Input76–7730077float32ABCDkvarh
Export reactive energySince last reset.Input78–7930079float32ABCDkvarh
Active power demandDoc label (Chinese): current active power demand.Input84–8530085float32ABCDW
Maximum active power demandInput86–8730087float32ABCDW
Current demandInput258–25930259float32ABCDA
Maximum current demandInput264–26530265float32ABCDA
Total active energyInput342–34330343float32ABCDkWh
Total reactive energyInput344–34530345float32ABCDkvarh
Resettable total active energyInput384–38530385float32ABCDkWh
Total active energy rate 1Input4876–487734877float32ABCDkWh
Total active energy rate 2Input4878–487934879float32ABCDkWh
Import active energy rate 1Input4884–488534885float32ABCDkWh
Import active energy rate 2Input4886–488734887float32ABCDkWh
Export active energy rate 1Input4892–489334893float32ABCDkWh
Export active energy rate 2Input4894–489534895float32ABCDkWh
Pulse output 1 widthWritable. Pulse on period in ms: 60, 100 or 200; default 100.Holding12–1340013float32ABCDms
Network parity/stopWritable. 0 = 1 stop bit no parity (default), 1 = 1 stop even, 2 = 1 stop odd, 3 = 2 stop no parity.Holding18–1940019float32ABCD
Network node (Modbus address)Writable. 1 to 247, default 1.Holding20–2140021float32ABCD
Network baud rateWritable. 0 = 2400, 1 = 4800, 2 = 9600 (default), 5 = 1200.Holding28–2940029float32ABCD

Check the firmware and document version of your device against the source; registers differ between versions. Found a mistake? Write to support@otdeck.com. Product names are trademarks of their owners; OTDeck is not affiliated with them.