Energy meter · Modbus RTU
Eastron SDM120CT Modbus register map
Single-phase CT-connected DIN-rail energy meter with RS-485 Modbus RTU. 30 registers below, copied from the vendor's document; OTDeck adds them to a connection with Register map → Add from library.
- Also covers
- SDM120CTM, SDM120CT-Modbus
- Link
- Modbus RTU (RS-485)
- Serial default
- 2400 baud, 8N1
- Unit id default
- 1
- Source
- Eastron SDM120CTM Smart Meter Modbus Protocol Implementation, V1.3
- Addresses
- The doc lists 3X/4X register references (30001 / 40001 based) together with the 'Modbus Protocol Start Address Hex'. Address here = reference - 30001 (input) or reference - 40001 (holding), which equals the hex start address printed in the doc (e.g. 30001 -> 0x0000, 30343 -> 0x0156). Source PDF is Jiaxing Eastron's own document, re-hosted by distributor Fastron Electronics in its 'Eastron Europe' folder.
Function codes 03, 04, 08 and 16 are valid; broadcast address not supported. 04 reads input (3X), 03 reads and 16 writes holding (4X) registers. All values are 32-bit IEEE 754 floats in two registers; start address and register count must be even. Defaults per doc: 2400 baud, one stop bit, no parity, meter ID 1. CT primary is set in holding 40051 (default 5 A). The doc's page header reads 'SDM120MVRTU Protocol' while its title is 'SDM120CTM Smart Meter Modbus Protocol Implementation V1.3'.
Registers
Address: the 0-based protocol address sent on the wire. Ref: the same register in 1-based notation (40001 = holding 0). Scale: multiply the raw value by it.
| Name | Table | Address | Ref | Type | Order | Scale | Unit |
|---|---|---|---|---|---|---|---|
| Voltage | Input | 0–1 | 30001 | float32 | ABCD | V | |
| Current | Input | 6–7 | 30007 | float32 | ABCD | A | |
| Active power | Input | 12–13 | 30013 | float32 | ABCD | W | |
| Apparent power | Input | 18–19 | 30019 | float32 | ABCD | VA | |
| Reactive power | Input | 24–25 | 30025 | float32 | ABCD | var | |
| Power factor | Input | 30–31 | 30031 | float32 | ABCD | ||
| Frequency | Input | 70–71 | 30071 | float32 | ABCD | Hz | |
| Import active energy | Input | 72–73 | 30073 | float32 | ABCD | kWh | |
| Export active energy | Input | 74–75 | 30075 | float32 | ABCD | kWh | |
| Import reactive energy | Input | 76–77 | 30077 | float32 | ABCD | kvarh | |
| Export reactive energy | Input | 78–79 | 30079 | float32 | ABCD | kvarh | |
| Total system power demand | Input | 84–85 | 30085 | float32 | ABCD | W | |
| Maximum total system power demand | Input | 86–87 | 30087 | float32 | ABCD | W | |
| Import system power demand | Input | 88–89 | 30089 | float32 | ABCD | W | |
| Maximum import system power demand | Input | 90–91 | 30091 | float32 | ABCD | W | |
| Export system power demand | Input | 92–93 | 30093 | float32 | ABCD | W | |
| Maximum export system power demand | Input | 94–95 | 30095 | float32 | ABCD | W | |
| Current demand | Input | 258–259 | 30259 | float32 | ABCD | A | |
| Maximum current demand | Input | 264–265 | 30265 | float32 | ABCD | A | |
| Total active energy | Input | 342–343 | 30343 | float32 | ABCD | kWh | |
| Total reactive energy | Input | 344–345 | 30345 | float32 | ABCD | kvarh | |
| Demand timeRead only. Minutes into first demand calculation. | Holding | 0–1 | 40001 | float32 | ABCD | min | |
| Demand periodWritable. 0-60 minutes, default 60; 0 = function closed. | Holding | 2–3 | 40003 | float32 | ABCD | min | |
| Relay pulse widthWritable. Relay on period in ms: 60, 100 or 200; default 100. | Holding | 12–13 | 40013 | float32 | ABCD | ms | |
| Network parity/stopWritable. 0 = 1 stop bit no parity (default), 1 = 1 stop even, 2 = 1 stop odd, 3 = 2 stop no parity. Restart required. | Holding | 18–19 | 40019 | float32 | ABCD | ||
| Meter ID (Modbus address)Writable. 1 to 247, default 1. | Holding | 20–21 | 40021 | float32 | ABCD | ||
| Baud rateWritable. 0 = 2400 (default), 1 = 4800, 2 = 9600, 5 = 1200. | Holding | 28–29 | 40029 | float32 | ABCD | ||
| CT1 primary currentWritable. CT primary current 5 to 9999, default 5. | Holding | 50–51 | 40051 | float32 | ABCD | A | |
| CT2 secondary currentWritable. 1 A or 5 A, default 5 A. | Holding | 52–53 | 40053 | float32 | ABCD | A | |
| Serial numberRead only. Register 464513 (0xFC00), unsigned int32. | Holding | 64512–64513 | 464513 | uint32 | ABCD |
Check the firmware and document version of your device against the source; registers differ between versions. Found a mistake? Write to support@otdeck.com. Product names are trademarks of their owners; OTDeck is not affiliated with them.
Download OTDeck, free for one connection All devices Modbus client