Eastron SDM120 Modbus register map

Single-phase DIN-rail energy meter with RS-485 Modbus RTU. 25 registers below, copied from the vendor's document; OTDeck adds them to a connection with Register map → Add from library.

Also covers
SDM120-Modbus, SDM120Modbus
Link
Modbus RTU (RS-485)
Serial default
2400 baud, 8N1
Unit id default
1
Source
Eastron SDM120Modbus Smart Meter Modbus Protocol Implementation (SDM120-Modbus RTU Protocol), V2.4
Addresses
The doc lists 3X/4X register references (30001 / 40001 based) together with the 'Modbus Protocol Start Address Hex'. Address here = reference - 30001 (input) or reference - 40001 (holding), which equals the hex start address printed in the doc (e.g. 30001 -> 0x0000, 30343 -> 0x0156). Source PDF is Zhejiang Eastron's own document, re-hosted by distributor Fastron Electronics in its 'Eastron Europe' folder.

Function codes 03, 04, 08 and 16 are supported; broadcast address not supported. 04 reads input (3X), 03 reads and 16 writes holding (4X) registers; in general one float per write. All values are 32-bit IEEE 754 floats in two registers (example response shows the high register first). Start address and register count must be even. Defaults per doc: 2400 baud, one stop bit, no parity, meter ID 1. Baud and parity changes are written as float codes (see holding registers). The SDM120CT has a separate protocol document.

Registers

Address: the 0-based protocol address sent on the wire. Ref: the same register in 1-based notation (40001 = holding 0). Scale: multiply the raw value by it.

NameTableAddressRefTypeOrderScaleUnit
VoltageInput0–130001float32ABCDV
CurrentInput6–730007float32ABCDA
Active powerInput12–1330013float32ABCDW
Apparent powerInput18–1930019float32ABCDVA
Reactive powerInput24–2530025float32ABCDvar
Power factorInput30–3130031float32ABCD
FrequencyInput70–7130071float32ABCDHz
Import active energyInput72–7330073float32ABCDkWh
Export active energyInput74–7530075float32ABCDkWh
Import reactive energyInput76–7730077float32ABCDkvarh
Export reactive energyInput78–7930079float32ABCDkvarh
Total system power demandInput84–8530085float32ABCDW
Maximum total system power demandInput86–8730087float32ABCDW
Import system power demandInput88–8930089float32ABCDW
Maximum import system power demandInput90–9130091float32ABCDW
Export system power demandInput92–9330093float32ABCDW
Maximum export system power demandInput94–9530095float32ABCDW
Current demandInput258–25930259float32ABCDA
Maximum current demandInput264–26530265float32ABCDA
Total active energyInput342–34330343float32ABCDkWh
Total reactive energyInput344–34530345float32ABCDkvarh
Relay pulse widthWritable. Relay on period in ms: 60, 100 or 200; default 100.Holding12–1340013float32ABCDms
Network parity/stopWritable. 0 = 1 stop bit no parity (default), 1 = 1 stop even, 2 = 1 stop odd, 3 = 2 stop no parity. Restart required.Holding18–1940019float32ABCD
Meter ID (Modbus address)Writable. 1 to 247, default 1.Holding20–2140021float32ABCD
Baud rateWritable. 0 = 2400 (default), 1 = 4800, 2 = 9600, 5 = 1200.Holding28–2940029float32ABCD

Check the firmware and document version of your device against the source; registers differ between versions. Found a mistake? Write to support@otdeck.com. Product names are trademarks of their owners; OTDeck is not affiliated with them.