OTDeck

Energy meter · Modbus RTU

ABB B23/B24 Modbus register map

ABB B-series three-phase DIN-rail energy meters (B23 direct connected 65 A, B24 CT connected) with RS-485 Modbus RTU. 59 registers below, copied from the vendor's document; OTDeck adds them to a connection with Register map → Add from library.

Also covers
B23, B24
Link
Modbus RTU (RS-485)
Source
B23/B24 User Manual, Document ID 2CMC485003M0201, Revision E (2025-11-07)
Addresses
The manual's mapping tables list 'Start Reg (Hex)' expressed exactly as sent on the bus (not to be reduced by 40000 or 1). Address here = that hex value (e.g. 5B00h = 23296).

Supported function codes: 3 (read holding), 6 (write single), 16 (write multiple). Readable range 0x1000-0x8EFF; any number of registers 1-125 may be read, outside the range gives exception 2. Multi-register values: most significant byte in the high byte of the first (lowest) register (big-endian, high word first). Unused/missing quantities return 'invalid': FFFF in all registers for unsigned, max positive (7FFF / 7FFFFFFF...) for signed. Writes to registers listed as writable but unsupported give no error; read back to confirm. RS485 Modbus settings on the display: parity None/Odd/Even, 1200-115200 baud, address 1-247; the manual does not list factory defaults. The RS485 port must be set to the Modbus protocol (it also supports EQ-Bus). Only models with an RS485 interface support Modbus RTU; the B21 single-phase meter has its own manual.

Registers

Address: the 0-based protocol address sent on the wire. Ref: the same register in 1-based notation (40001 = holding 0). Scale: multiply the raw value by it.

NameTableAddressRefTypeOrderScaleUnit
Active import energyResolution 0.01 kWh.Holding20480–20483420481uint64ABCD0.01kWh
Active export energyResolution 0.01 kWh.Holding20484–20487420485uint64ABCD0.01kWh
Active net energyResolution 0.01 kWh, signed.Holding20488–20491420489int64ABCD0.01kWh
Reactive import energyResolution 0.01 kvarh.Holding20492–20495420493uint64ABCD0.01kvarh
Reactive export energyResolution 0.01 kvarh.Holding20496–20499420497uint64ABCD0.01kvarh
Reactive net energyResolution 0.01 kvarh, signed.Holding20500–20503420501int64ABCD0.01kvarh
Apparent import energyResolution 0.01 kVAh.Holding20504–20507420505uint64ABCD0.01kVAh
Apparent export energyResolution 0.01 kVAh.Holding20508–20511420509uint64ABCD0.01kVAh
Active import tariff 1Resolution 0.01 kWh.Holding20848–20851420849uint64ABCD0.01kWh
Active import tariff 2Resolution 0.01 kWh.Holding20852–20855420853uint64ABCD0.01kWh
Active import tariff 3Resolution 0.01 kWh.Holding20856–20859420857uint64ABCD0.01kWh
Active import tariff 4Resolution 0.01 kWh.Holding20860–20863420861uint64ABCD0.01kWh
Active import L1Resolution 0.01 kWh.Holding21600–21603421601uint64ABCD0.01kWh
Active import L2Resolution 0.01 kWh.Holding21604–21607421605uint64ABCD0.01kWh
Active import L3Resolution 0.01 kWh.Holding21608–21611421609uint64ABCD0.01kWh
Active export L1Resolution 0.01 kWh.Holding21612–21615421613uint64ABCD0.01kWh
Active export L2Resolution 0.01 kWh.Holding21616–21619421617uint64ABCD0.01kWh
Active export L3Resolution 0.01 kWh.Holding21620–21623421621uint64ABCD0.01kWh
Resettable active importResolution 0.01 kWh.Holding21804–21807421805uint64ABCD0.01kWh
Resettable active exportResolution 0.01 kWh.Holding21808–21811421809uint64ABCD0.01kWh
Voltage L1-NHolding23296–23297423297uint32ABCD0.1V
Voltage L2-NHolding23298–23299423299uint32ABCD0.1V
Voltage L3-NHolding23300–23301423301uint32ABCD0.1V
Voltage L1-L2Holding23302–23303423303uint32ABCD0.1V
Voltage L3-L2Holding23304–23305423305uint32ABCD0.1V
Voltage L1-L3Holding23306–23307423307uint32ABCD0.1V
Current L1Holding23308–23309423309uint32ABCD0.01A
Current L2Holding23310–23311423311uint32ABCD0.01A
Current L3Holding23312–23313423313uint32ABCD0.01A
Current NHolding23314–23315423315uint32ABCD0.01A
Active power totalSigned 32-bit, 2 decimals (max about ±21 MW).Holding23316–23317423317int32ABCD0.01W
Active power L1Signed 32-bit, 2 decimals (max about ±21 MW).Holding23318–23319423319int32ABCD0.01W
Active power L2Signed 32-bit, 2 decimals (max about ±21 MW).Holding23320–23321423321int32ABCD0.01W
Active power L3Signed 32-bit, 2 decimals (max about ±21 MW).Holding23322–23323423323int32ABCD0.01W
Reactive power totalSigned 32-bit, 2 decimals (max about ±21 MW).Holding23324–23325423325int32ABCD0.01var
Reactive power L1Signed 32-bit, 2 decimals (max about ±21 MW).Holding23326–23327423327int32ABCD0.01var
Reactive power L2Signed 32-bit, 2 decimals (max about ±21 MW).Holding23328–23329423329int32ABCD0.01var
Reactive power L3Signed 32-bit, 2 decimals (max about ±21 MW).Holding23330–23331423331int32ABCD0.01var
Apparent power totalSigned 32-bit, 2 decimals (max about ±21 MW).Holding23332–23333423333int32ABCD0.01VA
Apparent power L1Signed 32-bit, 2 decimals (max about ±21 MW).Holding23334–23335423335int32ABCD0.01VA
Apparent power L2Signed 32-bit, 2 decimals (max about ±21 MW).Holding23336–23337423337int32ABCD0.01VA
Apparent power L3Signed 32-bit, 2 decimals (max about ±21 MW).Holding23338–23339423339int32ABCD0.01VA
FrequencyHolding23340423341uint160.01Hz
Phase angle power total-180 to +180.Holding23341423342int160.1°
Power factor total-1.000 to +1.000.Holding23354423355int160.001
Power factor L1-1.000 to +1.000.Holding23355423356int160.001
Power factor L2-1.000 to +1.000.Holding23356423357int160.001
Power factor L3-1.000 to +1.000.Holding23357423358int160.001
Current quadrant total1-4.Holding23358423359uint16
Output 1Writable. ON = 1, OFF = 0.Holding25344425345uint16
Output 2Writable. ON = 1, OFF = 0.Holding25345425346uint16
Serial numberHolding35072–35073435073uint32ABCD
Meter firmware versionASCII, e.g. 1.0.0, unused bytes 0.Holding35080–35087435081string[8]
Modbus mapping versionHigh byte = major, low byte = minor.Holding35088435089uint16
Type designationASCII, 12 characters including null termination.Holding35168–35173435169string[6]
Current tariffWritable. Tariff 1-4.Holding35335435336uint16
Power fail counterHolding35375435376uint16
CT ratio numeratorWritable (settings table: read and write).Holding35844–35845435845uint32ABCD
CT ratio denominatorWritable (settings table: read and write).Holding35848–35849435849uint32ABCD

Check the firmware and document version of your device against the source; registers differ between versions. Found a mistake? Write to support@otdeck.com. Product names are trademarks of their owners; OTDeck is not affiliated with them.