Docs · Commissioning tools
Point checkout
The point checkout (I/O checkout sheet) is the list a commissioning engineer walks point by point: “Supply temp reads 21 °C, matches the thermometer → pass”. OTDeck keeps one sheet per connection (or several), shows each point’s live value next to what you expect, records pass, fail or skip with the time and your name, and puts the result into a CSV and the commissioning report.
Open it
- Checkout in the toolbar of a protocol view (an icon only on screens narrower than 1280 px), or
- Point checkout: confirm each point… / Checkout of … in the command palette (⌘K / Ctrl+K).
Pick the connection and a sheet, or New sheet. The sheet’s name
defaults to “
Fill a sheet
Fill adds points; a point that is already on the sheet is merged, not added twice (its result and note stay; an empty name, unit or expectation is filled in):
| Source | What comes in |
|---|---|
| From the watch list | Modbus: every value of every register range; OPC UA and BACnet: the watch list (the open connection’s, else the saved one); every protocol: the values on the trend panel and in watch rules |
| From a snapshot | Modbus registers, OPC UA nodes, BACnet present values, MQTT topics (topics starting with $ left out) of a stored snapshot of a connection with the same protocol |
| Import CSV | A point list: name, address, expected, unit (see below) |
| Import EDE file (BACnet) | The input, output and value objects of an EDE 2.x main file, with their device, name and unit; device, schedule and other objects are left out |
| Add a point | One point by its address |
Addresses:
| Protocol | Address |
|---|---|
| MQTT | one topic (no + or #); a JSON field (value, a.b[2].c) or a Sparkplug B metric in their own columns |
| Modbus | a 40001-style reference (1-based: 40001 is holding register 0; six digits past 9999, 400100), or holding:0, input:9, coils:4, discrete:0 (0-based). The polled range that holds the address gives the type, byte and word order, scale and unit. |
| OPC UA | a node id (ns=2;s=Boiler.Temp) |
| BACnet | an object id (analog-input:1, or device:2601/analog-input:1); with one device on the connection the device is filled in |
CSV import
- With a header row, the columns can be in any order:
name(orpoint,tag,description),address(ortopic,node id,object,register,reference),expected,unit, and for MQTTfieldandmetric. Without a header the columns are name, address, expected, unit. OTDeck’s own CSV export imports back the same way. - The separator (
,,;or tab) is taken from the first line; a UTF-8 BOM is fine; lines starting with#are comments. - Bounds: at most 2 MB, 5000 rows and 1024 columns; names are cut at 200 bytes, expectations at 200, units at 32; control and bidi characters are dropped. A row whose address cannot be read is skipped with its line number in the result; a quoting error stops the import with its line.
- Results are not imported: a sheet’s results are always this visit’s.
Expected values
Type what you expect; the sheet shows how it reads it:
| You type | Read as | Checked automatically |
|---|---|---|
21 ± 0.5, 21 +/- 0.5, 21 ± 0.5 °C |
a number with tolerance | yes |
20..22, 20 – 22, 20 to 22 |
a range (both ends included) | yes |
21 |
exactly 21 | yes |
on, off, active, inactive, open, closed, run, stop, auto, manual, … or state: Auto 2 |
a state | yes: on matches active, true and 1, off matches inactive, false and 0; other states compare as text, without case |
| anything else (“matches the thermometer”) | free text | no: checked by eye |
Live values
The Live value column shows what OTDeck already holds, once a second; the sheet reads nothing from the devices itself: the OPC UA and BACnet watch lists, the last Modbus poll, the newest MQTT message (for a JSON field or a Sparkplug metric, the newest of the last 200 messages that has it). A word under the value says when it is not good, never a colour:
| Word | Meaning |
|---|---|
| stale | a Modbus poll failed, or a polled value (Modbus, BACnet polled) or an MQTT message is older than the sheet’s stale time (60 s by default, 5 s to 24 h in Rename, stale after…) |
| bad | bad OPC UA status, a BACnet fault flag or read error, an invalid Modbus value |
| uncertain | uncertain OPC UA status; a BACnet object out of service or overridden |
| retained | only the broker’s retained MQTT message so far |
| no value | not on the watch list (OPC UA, BACnet: Watch all adds the sheet’s points), no polled range holds the register, no message yet |
| offline | the connection is not open (results can still be set by hand) |
On BACnet sheets an Alarm column shows the event state the alarm monitor reads for the object (normal when the device was read whole and the object is not in its alarm list, — when it was not read or has more alarms than one read returns). A point added from the Alarms tab (Add to checkout…) expects its alarm to be back to normal: Check all now fails it while the object is in alarm or fault, and the recorded value carries the state (“72.1 °C · alarm normal”).
Check
- Keyboard: click a row (or focus the table), then Enter = pass, F = fail, S = skip, Backspace = not checked, ↑ ↓ (or J, K) move. After a result the next point not yet checked is selected. Keys typed into a field are never results, a held key records one result only, and when the filter hides the selected point the first key selects a shown one instead of recording.
- The buttons under the table do the same and edit the point’s name, expected value, unit and note.
- Each result records the time, your computer user name and the value shown at that moment (“21.4 °C”; a value that was not good keeps its word: “21.4 °C (stale)”).
- Check all now marks every point with a number, range or state Pass (auto) or Fail (auto) from its live value. A value that is stale, bad, uncertain, retained or missing never passes (the point stays as it was and the result says why). Points you set yourself are never changed by it; set one back to Not checked to let it be checked again.
- Filter: All, Not checked, Failed (a failed result or a failed command test).
- The progress line: “12 of 40 checked · 10 pass · 2 fail”.
Command test (Pro)
For a writable point (a Modbus coil or holding register in a polled range, an OPC UA node, a BACnet output or value object) the panel under the table has Command test: type a test value and Write test value.
- The value goes through the same write path as the protocol view’s write dialog: Pro, read-only connections refuse it, a production connection asks for its name, and the write log records it with the old and new value. Nothing is automatic and only one test runs at a time.
- OTDeck reads the value before the write, then reads the point back every 0.3 s for up to 5 s. Pass: the value read back is the one written (numbers within a relative 1e-5, states as above). Fail: it never came back; the sheet shows what was read. On BACnet a fail usually means a higher priority commands the object.
- Put it back by hand: Restore
writes the value read before the test; on a commandable BACnet object Relinquish priority N releases the priority the test wrote (12 by default, the connection’s write priority), so the object returns to what commanded it before. Both go through the write guard again (the production name is asked again) and into the write log. If the slot at that priority held a value before the test, relinquishing removes it: write it back from the BACnet view. - A second test before putting the first back keeps what to put back: the value read before the first test, and on BACnet the first test’s priority and device (a second test at another priority is refused until the first is relinquished).
- A test refused before anything was sent (not writable, no polled range, the guard, the plan) is shown as an error and not recorded on the sheet.
- MQTT points have no command test: publish to the command topic from the MQTT view.
Alarm test (Pro)
For a BACnet point that can report events (an analog, binary or multi-state object with intrinsic reporting, a loop, an accumulator, a pulse converter or an Event Enrollment object) the panel under the table has Alarm test: the end-to-end check of the alarm that every BMS acceptance protocol asks for.
- Pick what to expect: any alarm (offnormal, high-limit, low-limit), or one state (high-limit, low-limit, offnormal, fault); tick then back to normal to include the return; set the timeout (1 to 60 minutes, 5 by default).
- Start alarm test, then make the alarm happen yourself: heat or cool the sensor, command the output (the command test above, or the BACnet view), lower the limit in the head-end. OTDeck does not command the point: it only watches, so nothing here goes through the write guard.
- OTDeck reads the object’s alarm settings once (Event_State, Event_Enable, Notification_Class, limits, Time_Delay, Event_Detection_Enable) and the Recipient_List of its Notification Class, then reads Event_State every 2 s (5 s on a production connection) and looks at every event notification about the object that reaches OTDeck. The row shows what it waits for and the time left; Stop ends it (recorded as stopped; allowed on Free too).
A test starts only from normal: an object already in alarm or fault is refused with a message, and nothing is recorded.
| Verdict | When |
|---|---|
| pass | the expected state was seen (and normal again, when asked) and, when OTDeck is a recipient, its notification arrived |
| fail | the object went to another state (“went to fault, not high-limit”); the state changed but no notification reached OTDeck within 30 s (“check the Recipient_List of notification class 1 (OTDeck is 192.168.1.20:47808), its transitions, valid days and times, and that nothing drops UDP to OTDeck”); the device will not report the transition (Event_Enable without it, Event_Detection_Enable off, a Notification Class that does not exist) |
| timeout | Event_State did not change (or did not return to normal) within the timeout; the reason carries the limits and Time_Delay read at the start |
| stopped, interrupted | stopped by you; the connection closed, or OTDeck was closed during the test |
Notifications. When OTDeck is in the Recipient_List of the object’s class (Alarms → Recipients → Receive notifications here, or the head-end added this computer’s address with OTDeck’s process), the notification is part of the verdict, and the result keeps its class, priority, notify type, whether it needs an acknowledgement, when it arrived and OTDeck’s entry (“192.168.1.20:47808 · unconfirmed”). When OTDeck is not a recipient the verdict comes from Event_State alone and the result says the notification was not checked, and why. The warnings of the Configured tab (no to-normal, empty Event_Enable, event detection off, a missing class, an empty Recipient_List) are listed under the result.
At most 8 alarm tests run at once, one per point. The result stays on the point (a new test replaces it) and counts in the progress line (“2 alarm tests (1 failed)”); Failed shows failed and timed-out tests. The Pro check is in the app’s Go service, not only in the UI: Free sees the panel with a Pro hint and keeps every recorded result.
Export and the report (Pro)
- Export CSV saves the sheet: connection, protocol, name, address,
field, metric, unit, expected, how it was read, the value now, result,
how (auto or manual), the value observed, note, when, by whom, and the
command test (result, test value, old value, read back, restore), and
the alarm test (verdict, expected, started, reached, normal at, the
notifications or why they were not checked, the reason with the
settings warnings). Every
cell from a device or typed by you that a spreadsheet would run as a
formula (
=,+,-,@, tab, CR, and their full-width forms) starts with'. - The commissioning report dialog lists the sheets under Point checkout (optional); ticked ones (up to 16) get the section Point checkout after the snapshot comparison: per sheet the progress and every point with its address, expectation, observed value, result (pass and fail are the only coloured words), note, time and user, and the command test in words (“wrote 65 at priority 12, was 72.0 °C, read back 65.0 °C; priority relinquished”), and on a sheet with alarm tests an Alarm test column (verdict and the test in words: the transitions with their times, the notification with class and priority, the reason); the progress line adds “alarm tests: N passed, M failed”. At most 2000 rows in all; everything is escaped like the rest of the report.
Files
Sheets are kept in the app’s data folder, checkout/, one JSON file per
sheet (chk-<12 hex>.json), written atomically and readable only by you.
The file has a format version; a file from a newer OTDeck, a damaged one,
one larger than 8 MB or one that is not a regular file is listed with its
error. Bounds: 100 sheets, 2000 points per sheet. A sheet outlives its
connection: deleting the connection keeps the sheet and its results.
AI agents
No MCP tool reads or changes a checkout sheet, alarm tests included: results are the engineer’s. Agents keep their 17 tools.
Free and Pro
Free keeps one sheet of up to 25 points, with every fill, import, live value and check (also Check all now). Pro keeps up to 100 sheets of 2000 points, exports CSV, adds the report section, the command test and the alarm test. A sheet made on Pro stays readable and checkable on Free. See Licence and activation.